5.4
Baud rate setting/line length
The setting of the baud rate must be identical in all subscribers on the system bus.
The maximum possible baud rate is based on the necessary overall line length of the
system bus. The baud rate is set via the parameter
Baud-Rate
903 and thus defines
the possible line length.
Operation mode
Function
max. line length
3 - 50 kBaud
Transmission rate 50 kBaud
1000 meters
4 - 100 kBaud
Transmission rate 100 kBaud
800 meters
5 - 125 kBaud
Transmission rate 125 kBaud
500 meters
6 - 250 kBaud
Transmission rate 250 kBaud
250 meters
7 - 500 kBaud
Transmission rate 500 kBaud
100 meters
8 - 1000 kBaud
Transmission rate 1000 kBaud
25 meters
A baud rate under 50 kBaud, as defined according to CANopen, is not sensible for the
system bus as the data throughput is too low.
The maximum line lengths stated are guidelines. If they are made complete use of,
the admissible length is to be calculated on the basis of the line parameters and the
bus driver (PCA82C250T)
5.5
Setting node address
A maximum of 63 slaves or frequency inverters with system bus can be operated on
the system bus. Each frequency inverter is given a node ID, which may only exist
once in the system, for its unambiguous identification. The setting of the system bus
node ID is done via the parameter
Node-ID
900.
Parameter
Setting
No.
Description
Min.
Max.
Factory setting
900
Node-ID
-1 63
-1
Thus, the system bus possesses a maximum number of 63 subscribers (Network
nodes), plus one frequency inverter as a master.
Note:
With the factory setting of parameter
Node-ID
900 = -1, the system bus
is deactivated for this frequency inverter.
If the
Node-ID
900 = 0 is set, the frequency inverter is defined as a
master. Only one frequency inverter on the system bus may be defined
as a master.