EM-RES-03
15
10/07
10/07 EM-RES-03
15
5.2
Cables
For the bus line, use twisted a cable with harness shield (no foil shield).
Attention:
The control and communication lines are to be laid physically separate
from the power lines. The harness screen of the data lines is to be con-
nected to ground (PE) on both sides on a large area and with good con-
ductivity.
5.3
Socket X410B
The system bus is connected via three sockets of the plug X410B on the EM-RES-03
expansion module.
X410A
X410B
1
2 4
3 5
6
7
1
2 4
3 5
6
7
X410B
Socket X410B
Socket Input/Output
Description
X410B.1
Not connected
X410B.2
Digital input S1IND
X410B.3
Digital input S2IND
X410B.4
Digital input S3IND
Chapter
„Control inputs and outputs“
X410B.5 CAN-Low
CAN-Low (System bus)
X410B.6 CAN-High
CAN-High (System bus)
X410B.7 GND
CAN-GND (System bus)