Accessing data via PROFINET
26
Operating manual for PROFINET fieldbus | DOC01725815-0003 | 2016-12 | V2.04 EN
The first two process variables (control word and target value) cannot be parameterized and are
always expected. The remaining 4 process variables can be configured using parameters 6.110 to
6.113.
The "Process data In" available can be found in chapter
"Process data In". Use Vplus Dec,
MMI or PROFINET master for parameterization.
The structure of the "Process data In" set in the factory is shown in the following table.
Frame
no.
Address
Data
type
Designation
Unit
Description
1
0x0000
WORD*
Control word (see 4.2.1)
cannot be parameterized
2
0x0004
REAL***
Target value
%
cannot be parameterized
3
0x0008
DWORD**
Process data In 3
(Digital output 1
–
relay)
can be parameterized using
Vplus Dec tool (parameter 6.110)
4
0x000C
REAL
Process data In 4
(Analogue output 1)
V
can be parameterized using
Vplus Dec tool (parameter 6.111)
5
0x0010
Process data In 5
(Reserved)
can be parameterized using
Vplus Dec tool (parameter 6.112)
6
0x0014
Process data In 6
(Reserved)
can be parameterized using
Vplus Dec tool (parameter 6.113)
Tab.: 4 Process data In
*
WORD data type corresponds to UINT16 = 2 bytes
**
DWORD data type corresponds to UINT32 = 4 bytes
***
REAL data type corresponds to
= 4 bytes