Device and system description
Operating manual for PROFINET fieldbus | DOC01725815-0003 | 2016-12 | V2.04 EN
15
2.2.2
Pin assignment for interfaces
Pin assignment on device side of M12 socket for PROFINET:
PIN no.
Signal
1
TD +
2
RD +
3
TD -
4
RD -
Housing
Shielding
Fig. 8: Round plug connector, 4-pin, M12, D-coded for PROFINET fieldbus
2.2.3
Cable
The following points should be observed when wiring:
Lay bus and power cables as far apart as possible (min. 30 cm),
If cables do cross, an angle of 90° should be observed if possible.
2.3 Software components
What software do I require to operate and configure the drive controller with PROFINET.
The DGM drive controller can be parameterized using the Vplus Dec tool and MMI (see
operating manual) as well as the PROFINET master.