Quick Start Guide 

Agile

 

Applications via control terminals 

Select out-

put fre-

quency 

X12.1 

X… 

Fixed frequency change-over via two digital inputs. 

Set P492=3. Set frequency values in P480 ... 483. 

Select digital inputs P66 and P67.Select a frequency 

value via P66 und P67. 

Select digital inputs for P066 and P067:

71

X11.4

72

X11.5

73

X11.6 (P558=0)

74

X12.1

75

X12.2

76

X12.3 (P452=3 NPN or 4 PNP)

77

X12.4 (P562=3 NPN or 4 PNP)

P66 P67 Selection

Default

Hz 

0

0

P480

1

0

P481

10 

1

1

P482

25 

0

1

P483

50 

Data set 

change-over 

X11.6 

X… 

Fixed frequency change-over via two 

digital inputs. The four data sets can 

Include different parameter values. 

Select a data set via X11.6 and X12.1 

X11.6 X12.1

Selection 

0

0

DS 1

1

0

DS 2

1

1

DS 3

0

1

DS 4

Protection 

function 

X12.4 

Connect a motor thermal contact. 

Set P570: 1-Warning or 2-Error switch off. 

Voltage input for external voltage supply 

The external voltage supply enables the function of inputs, outputs and communication, even 

if the power supply of the frequency inverter is switched off. Refer to section “technical data 

of control terminals”. 

Data set 

Parameter values can be stored in four different data sets. 
If a data set is selected, the entered data is only stored in the selected data set. The other 

data sets contain standard values. If no data set is selected the entered data is stored in all 

four data sets. 

The data sets can be switched –over via control terminals (refer to section „Function of 

control terminals”). This enables the setting of different operating points of the drive or set-

tings for different motors. 

Example 1: Carry out auto-tuning and enter motor data in data set 1. 

data set

When setup is carried out the entered and measured motor data is stored in the selected 

data set. 

Example 2: set the motor rated voltage P370 in data set 2. 

 

Hold 

data set 

Value of P370 in data set 2 

Setup

ENT

DSet 0

ENT

DSet 1

DSet 4

...

P 370

DS

ENT

P 3701

+

P 3702

ENT

ENT

4002 U

P370, DS 2

Summary of Contents for agl 202

Page 1: ...Power Control Green Solutions T 31 0 88 7865800 F 31 0 88 7865899 E info elsto eu elsto eu Agile Quick Start Guide REQUENcy Inverter 6 6 0 09 kW 11 kW...

Page 2: ...When using communication interfaces and certain functions in example for the integrated PLC function the corresponding manual is additional to be complied with This Quickstartguide contains the descri...

Page 3: ...f the operation fix all covers assemble all components of the standard equipment and check the terminals No connection work may be performed while the power supply is switched on High voltage may appl...

Page 4: ...livery is complete Notify complaints to the supplier immediately Installation Indoors protected against weather influence Avoid direct sunlight exposure Avoid dust Keep away from strong electromagneti...

Page 5: ...arning High leakage current Warning Dangerous voltage Risk of electric shock Warning Hot surfaces 1 Labeling for Functional Safety if applicable Please check the Application manual Functional Safety 2...

Page 6: ...ssioning Assembly Frame size 1 Frame size 2 Frame size 3 Mains connection Motor connection Connection of control lines Comissioning Operation via control signals Operation via operator panel Setup via...

Page 7: ...ttom up or horizontal position is not permissible Screw the frequency inverter to a metallic not varnished mounting plate The frequency inverter must be earthed For potential equalization connect freq...

Page 8: ...g codes Connect mains supply 0 5 Nm Note Only required for DC link connection mm2 1 5 2 5 4 10 AWG 16 14 12 8 AWG American Wire Gauge American unit 3 400 V Type 02 11 13 15 18 19 21 22 23 kW 0 25 1 5...

Page 9: ...tched off Wait for several minutes before starting to work on the frequency inverter Make sure that the frequency inverter is de energized Ground the motor side grounding terminal Connect the motor Ca...

Page 10: ...16 25 35 35 50 U V W mm2 1 5 4 PE mm2 2 x 1 5 2 x 4 or 1 x 10 1 x 10 1 230 V Type 01 07 09 11 13 15 18 19 21 kW 0 09 0 37 0 55 0 75 1 1 1 5 2 2 3 0 3 0 F1 A 6 10 16 25 35 35 35 U V W mm2 1 5 PE mm2 2...

Page 11: ...t voltage outputs E Enable Start drive via control signals After Setup switch on start signals on X11 4 start clockwise or X11 5 start anticlockwise The drive is accelerated to 3 50 Hz default value o...

Page 12: ...in control method UF and Foc Entry of PoLPrS number of pole pairs in control method Synch Additional adjustments during commissioning setup Temperature evaluation at X12 4 via thermal contact PTC KTY...

Page 13: ...op the drive Cancel Return to the previous menu Reversal of rotation in mode Motorpoti Confirm settings Increase speed in mode Motor poti Scroll up to parameter numbers Increase parameter values Decre...

Page 14: ...e separate manual X12 6 CAN Low X11 1 DC 24 V output X11 2 GND for X11 1 X11 3 Digital input Input 1 for enable Contact opened output disabled motor coast to a standstill Contact closed together with...

Page 15: ...inverter overloaded Check load behavior Check motor parameter settings Overtemperature Check cooling fan sensor and ambient temperature Low temperature Check ambient temperature and electrical cabinet...

Page 16: ...efer to operating instructions manual P Parameter Digital Input Output X11 6 P558 0 input default 1 output Multifunction output X13 6 P550 1 digital MFO1D P554 10 analog PWM MFO1A default P553 20 repe...

Page 17: ...tch off Voltage input for external voltage supply The external voltage supply enables the function of inputs outputs and communication even if the power supply of the frequency inverter is switched of...

Page 18: ...TCP CM Modbus TCP 2P EtherNet IP CM EtherNet IP CM EtherNet IP 2P Communication interface X21 with RJ45 connection For serial RS485 communication via VA Bus or Modbus protocol BONFIGLIOLI Vectron pro...

Page 19: ...iguration TT TN IT Mains voltage range EN61800 5 1 U V AGL202 230 20 240 10 AGL402 380 15 480 10 Mains frequency f Hz 45 69 Overvoltage category EN 50178 III EN 61800 5 1 III Ambient conditions Coolin...

Page 20: ...brake resistor Minimum brake resistor R 100 100 100 100 100 100 100 100 Recommended brake resis tor 385 V R 300 220 250 200 220 140 200 100 Input mains side Rated current I A 1 7 1 2 1 9 1 4 2 5 2 0 3...

Page 21: ...ake resistor Minimum brake resistor R 100 100 100 100 37 37 37 37 Recommended brake resistor 385 V R 100 100 100 100 92 63 70 41 Input mains side Rated current I A 4 2 3 4 5 3 4 9 7 6 6 5 11 2 9 5 Max...

Page 22: ...tor Minimum brake resistor R 18 5 18 5 18 5 18 5 Recommended brake resis tor 385 V R 72 37 41 27 Input mains side Rated current I A 14 2 12 5 19 5 17 0 Maximum mains current 1 I A 20 6 18 5 28 0 25 5...

Page 23: ...or Minimum brake resistor R 18 5 18 5 18 5 18 5 Recommended brake resistor 385 V R 32 19 32 18 5 Input mains side Rated current I A 26 7 22 5 26 7 30 0 Maximum mains current 1 I A 40 0 33 0 40 0 41 5...

Page 24: ...resistor R 300 300 300 300 300 220 220 Recommended brake resistor 770V R 2432 1594 930 634 462 300 220 Input mains side Rated current I A 0 8 1 2 1 8 2 4 2 8 3 3 5 8 Maximum mains current 1 I A 1 1 1...

Page 25: ...6 106 48 48 48 48 Recommended brake resistor 770 V R 148 106 106 80 58 48 48 Input mains side Rated current I A 6 8 7 8 13 8 14 2 15 8 20 0 26 0 Maximum mains current 1 I A 9 8 12 8 17 2 17 2 23 0 28...

Page 26: ...on Multifunction Digital input output X11 6 Default digital input Refer to table row Digital inputs Can be configured as digital output by means of P558 Output Uout DC 22 V DC 15 30 V Imax 100 mA Imax...

Page 27: ...Voorhout Groningen Weert Hoogerheide T 31 0 88 7865800 I elsto eu...

Page 28: ...en lineaire aandrijvingen componenten en regelaars Engineering en productie van speciale aandrijvingen Engineering en productie van besturingsoplossingen en paneelbouw Verkoop van frequentieregelaars...

Reviews: