Quick Start Guide
Agile
Applications via control terminals
Select out-
put fre-
quency
X12.1
X…
Fixed frequency change-over via two digital inputs.
Set P492=3. Set frequency values in P480 ... 483.
Select digital inputs P66 and P67.Select a frequency
value via P66 und P67.
Select digital inputs for P066 and P067:
71
X11.4
72
X11.5
73
X11.6 (P558=0)
74
X12.1
75
X12.2
76
X12.3 (P452=3 NPN or 4 PNP)
77
X12.4 (P562=3 NPN or 4 PNP)
P66 P67 Selection
Default
Hz
0
0
P480
0
1
0
P481
10
1
1
P482
25
0
1
P483
50
Data set
change-over
X11.6
X…
Fixed frequency change-over via two
digital inputs. The four data sets can
Include different parameter values.
Select a data set via X11.6 and X12.1
X11.6 X12.1
Selection
0
0
DS 1
1
0
DS 2
1
1
DS 3
0
1
DS 4
Protection
function
X12.4
Connect a motor thermal contact.
Set P570: 1-Warning or 2-Error switch off.
Voltage input for external voltage supply
The external voltage supply enables the function of inputs, outputs and communication, even
if the power supply of the frequency inverter is switched off. Refer to section “technical data
of control terminals”.
Data set
Parameter values can be stored in four different data sets.
If a data set is selected, the entered data is only stored in the selected data set. The other
data sets contain standard values. If no data set is selected the entered data is stored in all
four data sets.
The data sets can be switched –over via control terminals (refer to section „Function of
control terminals”). This enables the setting of different operating points of the drive or set-
tings for different motors.
Example 1: Carry out auto-tuning and enter motor data in data set 1.
data set
When setup is carried out the entered and measured motor data is stored in the selected
data set.
Example 2: set the motor rated voltage P370 in data set 2.
Hold
data set
Value of P370 in data set 2
Setup
ENT
DSet 0
ENT
DSet 1
DSet 4
...
P 370
DS
ENT
P 3701
+
P 3702
ENT
ENT
4002 U
P370, DS 2