Quick Start Guide
Agile
32
05/2013
Mains connection
Danger!
Switch off power supply
Dangerous voltage: The power terminals may carry dangerous voltages for some time even if
the power supply is switched off. Wait for some minutes before starting to work at the
frequency inverter.
Make sure that the frequency inverter is de- energized.
Do not carry out high voltage insulation tests on cable connect to the frequency inverter.
Follow local wiring codes
Connect mains supply.
0,5
Nm
Note:
Only required for DC-
link connection.
mm
2
1,5
2,5
4
10
AWG
16
14
12
8
AWG: American Wire Gauge
(American unit)
3~400 V
Type
-02…-11 -13 -15 -18 -19 -21 -22 -23
kW
0.25…1.5 2.2 3.0 4.0 5.5 7.5 9.2 11
F1
A
6
10 10 10 16 25 35 35
L1, L2, L3 mm
2
1.5
2.5
4
PE
mm
2
2 x 1.5
2 x 2.5
2 x 4
or
1 x 10
1 x 10
1 x 10
3~230 V
Type -01…-07
-09 -11…-13 -15 -18 -19 -21
kW
0.18…0.75
1.1 1.5…2.2 3.0 4.0 5.5 7.5
F1
A
6
10
16
25
35 35 50
L1, L2, L3 mm
2
1.5
2.5
4
6
PE
mm
2
2 x 1.5
2 x 2.5
2 x 4
2 x 6
or
1 x 10
1 x 10
1 x 10
1x10
1~230 V
Type -01…-07
-09 -11…-13 -15 -18 -19 -21
kW
0.09…0.37
0.55
0.75…1.1
1.5 2.2 3.0 3.0
F1
A
6
10
16
25
35
35
L1, N
mm
2
1,5
2,5
4
PE
mm
2
2 x 1,5
2 x 2,5
2 x 4
or
1 x 10
1 x 10
1 x 10
B