Default function and settings
Start clockwise (cw) via rising signal edge or
Start anticlockwise (ccw) via rising signal edge.
Application
T
Reference speed 0 ... 10 VDC at analog input. P452=1-voltage (default). 0 V corresponds
to 3.50 Hz (default value of P418). 10 V corresponds to 50 Hz (default value of P419).
Stop
Start
Set motor speed
Input signals
Fixed frequency change-over via
two digital inputs. Set P492=3. Set
frequency values in P480 ... 483.
Select a frequency value via
P66 and P67.
Select digital inputs for P66 and
P67.
Data set
change-over
Select output
frequency
X11.3
Function
24 VDC
GND for terminal X13.1
T
GND
Voltage input
X13.1
X13.2
24 VDC
GND for terminal X11.1
GND
Voltage output X11.1
X11.2
10 VDC
Voltage output X13.4
X12.3
P66 P67 Selection
0
0
P480
1
0
P481
1
1
P482
0
1
P483
Default
0 Hz
10 Hz
25 Hz
50 Hz
Data set change-over via two digital inputs. The four data sets
can include different parameter values. Select a data set via
X11.6 and X12.1.
X13.3
Enable: digital signals at both terminals.
X11.4
X11.5
X11.3
X13.3
Disable: Reset digital signal on at least one terminal.
AND
Change direction
of rotation
Reset Start clockwise or
Reset Start anticlockwise.
X11.4
X11.5
OR
Output signals
Actual
frequency
Voltage signal proportional to frequency
(speed). At 50 Hz (P419) output of 10 VDC.
At 0 Hz output of 0 VDC.
X11.6 X12.1 Selection
0
0
Data set 1
1
0
Data set 2
1
1
Data set 3
0
1
Data set 4
Function
T
X13.6
Operational
state
X13.5 Run signal. Indicates enable and start
command. Output frequency available.
Protection function
Motor
temperature
Connect a motor thermal contact.
Set P570: 1 Warning or 2 Error switch-off.
Function and settings
Application
T
X12.4
Applications via control terminals
X
Voltage input and outputs
Extended settings of control terminals
Voltage input for external voltage supply
The external voltage supply enables the function of inputs, outputs and communication, even if the power supply of
the frequency inverter is switched off. Refer to section “Technical data of control terminals”.
X11.6
X12.1
X11.3 X13.3 X11.4
1
1
1
1
1
1
1
1
0
1
0
1
Enable
Start cw
12
1-digital
2-analog (default)
3-repetition frequency
4-pulse train
P550
Multifunction output
X13.6
Default:
1-: Signal when output frequency exceeds 3 Hz (P510).
2-: Output of voltage proportional to speed.
3-: Frequency output. 0...24 V propotional to speed.
4-: Output of pulse train, scaled by P557.
NPN: LOW-switching (on negative signal). Default of P562.
PNP: HIGH-switching (on positive signal). Default of P559.
P559
Switchable logic of digital inputs
X11.4
X11.5
X11.6
X12.1
X12.2
X12.3
1-PNP
0-NPN
P452
4-digital input PNP
3-digital input NPN
X12.4 P562
4-digital input PNP
3-digital input NPN
0-input (default)
1-output
P558
Digital input/output
X11.6
1-voltage 0...10V
2-current 0...20mA
3-digital NPN
4-digital PNP
5-current 4...20mA
6-voltage, characteristic
7-current, characteristic
6-: programmable characteristic via P454...457
7-: programmable characteristic via P564...567
(Refer to operating instructions manual.)
P452
Multifunction input
X12.3
P562
X12.4
X11.5
0
0
1
1
Start ccw
Stop
P554
P553
P555
P557
Select
signal.
Scaling.
X
71
72
73
74
75
76
77
Digital inputs
X11.4
X11.5
X11.6
X12.1
X12.2
X12.3 (P452=3 NPN or 4 PNP)
X12.4
(P558=0)
(P562=3 NPN or 4 PNP)
GB