Default function and settings

Start clockwise (cw) via rising signal edge or
Start anticlockwise (ccw) via rising signal edge.

Application

T

Reference speed 0 ... 10 VDC at analog input. P452=1-voltage (default). 0 V corresponds
to 3.50 Hz (default value of P418). 10 V corresponds to 50 Hz (default value of P419).

Stop

Start

Set motor speed

Input signals

Fixed frequency change-over via
two digital inputs. Set P492=3. Set
frequency values in P480 ... 483.

Select a frequency value via

P66 and P67.

Select digital inputs for P66 and
P67.

Data set
change-over

Select output
frequency

X11.3

Function

24 VDC
GND for terminal X13.1

T

GND

Voltage input

X13.1
X13.2

24 VDC
GND for terminal X11.1

GND

Voltage output X11.1

X11.2

10 VDC

Voltage output X13.4

X12.3

P66 P67 Selection

0

0

P480

1

0

P481

1

1

P482

0

1

P483

Default

0 Hz

10 Hz

25 Hz

50 Hz

Data set change-over via two digital inputs. The four data sets
can include different parameter values. Select a data set via
X11.6 and X12.1.

X13.3

Enable: digital signals at both terminals.

X11.4
X11.5

X11.3
X13.3

Disable: Reset digital signal on at least one terminal.

AND

Change direction
of rotation

Reset Start clockwise or
Reset Start anticlockwise.

X11.4
X11.5

OR

Output signals

Actual
frequency

Voltage signal proportional to frequency
(speed). At 50 Hz (P419) output of 10 VDC.
At 0 Hz output of 0 VDC.

X11.6 X12.1 Selection

0

0

Data set 1

1

0

Data set 2

1

1

Data set 3

0

1

Data set 4

Function

T

X13.6

Operational
state

X13.5 Run signal. Indicates enable and start

command. Output frequency available.

Protection function

Motor
temperature

Connect a motor thermal contact.
Set P570: 1 Warning or 2 Error switch-off.

Function and settings

Application

T

X12.4

Applications via control terminals

X

Voltage input and outputs

Extended settings of control terminals

Voltage input for external voltage supply

The external voltage supply enables the function of inputs, outputs and communication, even if the power supply of
the frequency inverter is switched off. Refer to section “Technical data of control terminals”.

X11.6
X12.1

X11.3 X13.3 X11.4

1
1
1
1

1
1
1
1

0
1
0
1

Enable
Start cw

12

1-digital
2-analog (default)
3-repetition frequency
4-pulse train

P550

Multifunction output
X13.6

Default:
1-: Signal when output frequency exceeds 3 Hz (P510).
2-: Output of voltage proportional to speed.
3-: Frequency output. 0...24 V propotional to speed.
4-: Output of pulse train, scaled by P557.

NPN: LOW-switching (on negative signal). Default of P562.
PNP: HIGH-switching (on positive signal). Default of P559.

P559

Switchable logic of digital inputs
X11.4
X11.5
X11.6
X12.1
X12.2

X12.3

1-PNP

0-NPN

P452

4-digital input PNP

3-digital input NPN

X12.4 P562

4-digital input PNP

3-digital input NPN

0-input (default)
1-output

P558

Digital input/output
X11.6

1-voltage 0...10V
2-current 0...20mA
3-digital NPN
4-digital PNP
5-current 4...20mA
6-voltage, characteristic
7-current, characteristic

6-: programmable characteristic via P454...457
7-: programmable characteristic via P564...567
(Refer to operating instructions manual.)

P452

Multifunction input
X12.3

P562

X12.4

X11.5

0
0
1
1

Start ccw
Stop

P554
P553
P555
P557

Select
signal.

Scaling.

X

71

72

73

74

75

76

77

Digital inputs

X11.4

X11.5

X11.6

X12.1

X12.2

X12.3 (P452=3 NPN or 4 PNP)

X12.4

(P558=0)

(P562=3 NPN or 4 PNP)

GB

Summary of Contents for Agile AGL 401-05

Page 1: ......

Page 2: ...anical equipment erection Before commissioning and the start of the operation fix all covers assemble all components of the standard equipment and check the terminals No connection work may be perform...

Page 3: ...material Provide sufficient cooling Install fans when installing the frequency inverter inside an enclosed cabinet Installation place On opening the package Make sure that the delivered product is th...

Page 4: ...Recommended motor shaft power 09 11 13 15 0 55 kW 05 07 0 75 kW 4 0 kW 18 5 5 kW 19 7 5 kW 21 9 2 kW 22 1 1 1 1 1 2 2 3 3 3 Refer to the corresponding section Frequency Inverter AGL 401 05 Output Pow...

Page 5: ...up or horizontal position is not permissible Warning Screw the frequency inverter to a metallic not varnished mounting plate The frequency inverter must be earthed For potential equalization connect f...

Page 6: ...ables connected to the frequency inverter Use copper wire rated at 30 C B B Only required for DC link connections 3 400 V 400 V PE L3 L2 L1 F1 F1 F1 0 5 Nm AWG mm 2 2 5 14 12 4 1 5 16 8 10 X1 GB d d d...

Page 7: ...ded control cables Connect the conductor shielding of the control cables to ground potential by means of the shielding clamp Connect the conductor shielding to ground potential on both sides of the ca...

Page 8: ...start clockwise or X11 5 start anticlockwise The drive is accelerated to 3 50 Hz default value of P418 Start drive via key of operator panel After Setup select function Motorpoti menu refer to section...

Page 9: ...p Choose data set 0 Another setting is only necessary for setup of various motors Dset 0 ENT Acc Acceleration clockwise ENT 500 5 00 Hz s 501 499 ENT DEC done Deceleration clockwise Setup can be selec...

Page 10: ...s to increment or decrement each digit separately 501 499 P 421 P 419 Switch on Enable on X11 3 and X13 3 Switch off start commands on X11 4 and X11 5 Set Jog frequency via P489 Default 5 Hz ENT COpy...

Page 11: ...r sensor defective Check connection on X12 4 Phase failure Check motor and wiring F0500 F0507 Overloaded s heck load behavior and ramps P420 P423 C hort circuit or earth fault motor current or phase f...

Page 12: ...ion T 24 VDC input X13 1 GND for X13 1 X13 2 Digital input Input 2 for enable Contact opened output disabled motor coast to a standstill Contact closed together with X11 3 normal operation X13 3 10 VD...

Page 13: ...ble Protection function Motor temperature Connect a motor thermal contact Set P570 1 Warning or 2 Error switch off Function and settings Application T X12 4 Applications via control terminals X Voltag...

Page 14: ...rter Power of the motor at the current operating point Motor speed Output frequency of the inverter actual frequency of the motor The cause of error switch off F0102 Warning because of a critical cond...

Page 15: ...uency A 6 6 10 10 3 9 7 3 Size 1 C Communication Optional module Connection X21 W 2 4 8 16 Storage Digital memory card Save and transfer parameter values via standard memory card UL type 600 VAC RK5 3...

Page 16: ...1000 depending on switching frequency UL type 600 VAC RK5 A 10 10 25 20 25 20 35 30 9 8 133 15 0 11 2 7 5 17 2 235 26 0 19 5 13 0 23 0 321 34 0 25 5 17 0 28 1 393 38 0 30 0 20 0 Size 2 3 C Communicati...

Page 17: ...Frequency signal f 150 kHz pwm max Multifunction X11 6 X12 3 X12 4 Default digital input Default analog voltage input Can be configured as analog current input or digital input by means of P452 Defaul...

Page 18: ...deckungen angebracht alle zur Standardausr stung des Frequenzumrichters geh rigen Bauteile installiert sein und die Klemmen berpr ft werden Wenn die Spannungsversorgung eingeschaltet ist d rfen keine...

Page 19: ...icht in der N he von entflammbarem Material Auf ausreichende K hlung achten L fter installieren wenn der Frequenzumrichter in einen geschlossenen Schaltschrank installiert wird Installationsort Nach d...

Page 20: ...pfohlene Motorwellenleistung 09 11 13 15 0 55 kW 02 03 0 75 kW 4 0 kW 18 5 5 kW 19 7 5 kW 21 9 2 kW 22 1 1 1 1 1 2 2 3 3 3 Siehe entsprechenden Abschnitt Frequency Inverter AGL 401 05 Output Power Con...

Page 21: ...den Warnung Den Frequenzumrichter an eine metallische nicht lackierte Montagefl che schrauben Der Frequenzumrichter muss geerdet sein F r einen Potentialausgleich den Frequenzumrichter Schaltschr nke...

Page 22: ...ssenen Leitungen d rfen keiner Isolationspr fung mit hoher Pr fspannung ausgesetzt werden Kupferleitungen f r 30 C Umgebungstemperatur verwenden B B Nur f r Anschl sse am Gleichspannungszwischenkreis...

Page 23: ...rm der Steuerleitungen mit Hilfe einer Schirmschelle erden Den Leitungsschirm an beiden Enden des Kabels erden Analoge Steuerleitungen nur in der N he des Frequenzumrichters erden Steuerleitungen von...

Page 24: ...er Start links an X11 5 einschalten Der Motor wird auf 3 50 Hz Werkseinstellung von P418 beschleunigt Den Motor mit dem Bedienfeld starten Nach der Inbetriebnahme Setup die Funktion Motorpoti w hlen M...

Page 25: ...Men gew hlt wurde Datensatz 0 w hlen Eine andere Einstellung ist nur f r die Inbetriebnahme von mehreren Motoren erforderlich Datensatzauswahl Dset 0 ENT Acc Acceleration Beschleunigung Rechtslauf EN...

Page 26: ...oder f r 1 s dr cken um jede Ziffer einzeln zu erh hen oder zu verringern 501 499 P 421 P 419 Motordaten CTRL Regelungsverfahren und Motortyp ENT ENT UF FoC SYNCH Freigabe an X11 3 und X13 3 einschal...

Page 27: ...03 Motortemperatur zu hoch oder Temperatursensor defekt Anschluss an X12 4 pr fen Phasenfehler Motor und Anschl sse pr fen F0500 F0507 berlast Kurzschluss oder Erdschluss Motorstrom oder Phasenfehler...

Page 28: ...ngang X13 1 Masse GND f r X13 1 X13 2 Digitaleingang Eingang 2 f r Freigabe Kontakt ge ffnet Motorauslauf bis Stillstand Kontakt geschlossen zusammen mit X11 3 Normalbetrieb X13 3 10 VDC Ausgang X13 4...

Page 29: ...nen Motor Thermokontakt anschlie en P570 einstellen 1 Warnung oder 2 Fehlerabschaltung Funktion Anwendung K X12 4 Anwendungen der Steuerklemmen X Spannungseing nge und Spannungsausg nge Erweiterte Ein...

Page 30: ...torleistung im derzeitigen Betriebspunkt Motordrehzahl Ausgangsfrequenz des Frequenzumrichters Istdrehfrequenz des Motors Die Ursache einer Fehlerabschaltung F0102 Warnung aufgrund eines kritischen Be...

Page 31: ...nz A 6 6 10 10 3 9 7 3 Baugr e 1 C Kommunikation Optionale Module Anschluss X21 W 2 4 8 16 Speicherung Digitale Speicherkarte Speichern und bertragen von Parameterwerten UL 600 VAC RK5 3 0 40 40 55 mi...

Page 32: ...abh ngig von Schaltfrequenz UL type 600 VAC RK5 A 10 10 25 20 25 20 35 30 9 8 133 15 0 11 2 7 5 17 2 235 26 0 19 5 13 0 23 0 321 34 0 25 5 17 0 28 1 393 38 0 30 0 20 0 Baugr e 2 3 C Kommunikation W 2...

Page 33: ...kHz pwm max Multifunktion X11 6 X12 3 X12 4 Werkseinstellung Eingang Werkseinstellung analoger Spannungseingang Kann ber P452 als analoger Stromeingang oder als Digitaleingang eingestellt werden Werks...

Page 34: ...w w w b o n f i g l i o l i c o m...

Reviews: