8

 

MAINTENANCE AND REPAIR 

8.1

 

At least once a year the following maintenance works shall be performed: 
-

 

Inspection for visible physical damage; 

-

 

Visual checking of dust on the surface of the insect screen. In case of any dust, remove it with a vacuum cleaner (by pumping of air). 

At least once every two years check the detector operability as described in Clause 7 of this manual. 

8.2

 

When the detector indicators flash triply every 6 s, which indicates the Contaminated Chamber conditions, clean the sensing chamber by doing the 

following: 

1)

 

Remove the detector from the base as described in Clause 5.5 of this manual. 

2)

 

Remove the detector cover (Figure 1, Position 6) from the detector body by holding it by the stiffeners and rotating it slightly counterclockwise. 

Then take out one-by-one the sensing chamber cover (Figure 1, Position 7) and the screen (Figure 1, Position 8). 

3)

 

Clean the sensing chamber cover, the screen, and the sensing chamber itself with a soft brush. 

W A R N I N G !   The  sensing  chamber  shall  be  mandatory  cleaned  when  the  smoke  detector  enters  the  Contaminated  Chamber  conditions. 
Otherwise, this can trigger false alarms. 

8.3

 

Maintenance  of  the  detector  as  a  part  of  a  fire  alarm  system  is  to  be  arranged  in  accordance  with  the  technical  guide  “Maintenance  of  fire  alarm 

systems  and  public  address  and  general  alarm  systems  of  type  1-2  in  Orion  ISS”,  and  maintenance  of  the  detector  as  a  part  of  a  fire  extinguishing 
installation  is  to  be  arranged  as  per  the  technical  guide  “Maintenance  of  fixed  fire  suppression  systems  based  on  S2000-ASPT  Fire  Alarm  and 
Extinguishing Control Unit”. 
8.4

 

When the light indicators of the detector issue four flashes spaced 200 ms apart every 6 s, which means the Fault condition, the detector needs to be 

repaired.  A  defective  detector  is  subject  to  repair  by  the  manufacturer  or  in  authorized  repair  centers.  While  submitting  the  product

 

for  repair,  please 

always apply a report describing the possible failure to it. 

W A R N I N G !   T h e   m a n u f a c t u r e r   d o e s   n o t   a c c e p t   a n y   c l a i m s   w i t h o u t   a   m a l f u n c t i o n   r e p o r t   a p p l i e d . 

8.5

 

A product’s failure resulted from consumer’s not observing mounting or operation rules shall not be a reason for claims and warranty repair. 

W A R N I N G !

 

Do not try to remove the printed circuit board; this will automatically void the warranty liabilities. 

8.6

 

Claims should be submitted to the following address: 
NVP BOLID, #4 Pionerskaya Str., Korolyov, Moscow Region, 141070, Russia 
Tel./fax: 

+7 (495) 775-71-55

 (PBX). E-mail: 

[email protected]

.  

8.7

 

In case of any issue related to use of the product, please contact the technical support: +7 (495) 775-71-55 or e-mail: 

[email protected]

.  

9

 

TRANSPORTING, STORAGE, DISPOSAL 

9.1

 

The detectors in a transport container are to be transported by any type of covered vehicles in accordance with the requirements of actual regulatory 

documents. 
9.2

 

The detectors shall be stored in consumer packages in heated warehouse premises at temper5

°

С

 t40

°

С

 and relative humidity up to 

80% at +20

°

С

9.3

 

In  a  transport  container  the  detectors  can  be  stored  in  unheated  warehouse  premises  at  ambient  temperatures -50

°

С

  through  +50

°

С

  and  relative 

humidity up to 95% at +35

°

С

9.4

 

The detector should be disposed of considering that there are no toxic components in it. The detector’s enclosure is made of recyclable ABS plastic.  

9.5

 

The content of precious materials: does not require accountability for storage, retirement and disposal (Clause 1.2 of GOST 2.608-78). 

9.6

 

The content of non-ferrous metals: does not require accountability for retirement and further disposal. 

10

 

MANUFACTURER WARRANTY 

The warranty period is 18 months since the day of putting the detector into operation but no more than 24 months from the manufacturer’s date of 

production. 

11

 

CERTIFICATION INFORMATOIN 

11.1

 

DIP-31 complies  with  the  requirements  of  Technical  Regulations  “On  Fire  Safety  Requirements”  (Federal  Law  No.123-FZ  dated  July  22,  2008, 

GOST R 53325-2012) and is awarded with Conformity Certificate No. C-RU.

ЧС

13.

В

.001193. 

11.2

 

DIP-31  complies  with  the  requirements  of  Technical  Regulations  of  Custom  Union  TR  CU  020/2011  and  is  awarded  with  Declaration  of 

Conformity 

ЕАЭС

 

 RU 

Д

-RU.

МЕ

61.

В

.00019/18. 

11.3

 

DIP-31  complies  with  the  requirements  of  Technical  Regulations  TR  EAEU  037/2016  “On  the  restriction  of  the  use  of  hazardous  substances  in 

electronic and radio electronic equipment” and is awarded with Declaration of Conformity 

ЕАЭС

 

 RU 

Д

-RU.

РА

01.

В

.21887/20. 

12

 

INFORMATION ON ACCEPTANCE, PACKAGING, AND MARKING 

12.1

 

IP 212-31  DIP-31 threshold  photoelectric smoke  detectors are  manufactured,  accepted  in  line  with  mandatory  requirements  of  national standards 

and actual technical documentation, approved as ready for operation, and packaged. 
12.2

 

The detector is marked with its factory number, quarter and year of production on its enclosure, and the BOLID trademark is placed on the detector 

body and the package. 

Summary of Contents for IP 212-31 DIP-31

Page 1: ...ensitivity dB m 0 05 to 0 2 2 2 Rated power voltage V 24 2 3 Consumed current In the quiescent mode uA 140 max In the fire alarm mode mA 10 max 2 4 Internal resistance of the detector in the Fire Alarm mode at the current value 8 mA 2 6 kOhm max 2 mA 4 5 kOhm max 2 5 Start up time s 40 max 2 6 Operating temperature range С Minus 10 through 55 2 7 Relative air humidity Up to 93 at 40 С 2 8 Enclosur...

Page 2: ... holes into the surface according to the drilling pattern in Figure 2 and attach the base by means of screws and wall plugs or tapping screws 5 2 To install the detector onto fire resistant tiles of suspended ceiling use MK 2 or MK 3 mounting kit for attaching the detector base Figure 3 Position 1 Make a mounting hole for the mounting kit according to the marking Figure 3 5 3 Until installation wo...

Page 3: ...ured levels of sensing chamber signal are 75 of the fire condition level FIRE ALARM Light steadily CONTAMINATED CHAMBER Three flashes every 6 s if the signal level has slowly reached 75 percent of the maximum contamination level Drift compensation is performed every 24 hours FAULT Four flashes spaced 200 ms apart every 6 s if the measuring function of the detector is out of order 7 TESTING 7 1 App...

Page 4: ...mitted to the following address NVP BOLID 4 Pionerskaya Str Korolyov Moscow Region 141070 Russia Tel fax 7 495 775 71 55 PBX E mail info bolid ru 8 7 In case of any issue related to use of the product please contact the technical support 7 495 775 71 55 or e mail support bolid ru 9 TRANSPORTING STORAGE DISPOSAL 9 1 The detectors in a transport container are to be transported by any type of covered...

Reviews: