THRESHOLD PHOTOELECTRIC SMOKE DETECTOR

 

IP 212-31 DIP-31

 

 

OPERATIONS MANUAL 

1

 

GENERAL 

1.1

 

IP 212-31 DIP-31  Threshold  Photoelectric  Smoke  Detector  (hereinafter  referred  to  as  the  detector)  is  to  be  used  in  fire  detection  and  fire  alarm 

systems  to  detect  smoke  producing  fires  in  closed  premises  of  buildings  by  sensing  the  light  reflected  by  smoke  particles  in  its  sensing  chamber  and 
sending a fire alarm. 
1.2

 

Two LEDs on the detector provide information on the detector’s conditions, which can be Quiescent Conditions, Pre-Alarm, Fire Alarm, Fault, and 

Contaminated Chamber. 
1.3

 

The  detector  is  to  be  brought  into  an  alarm  loop  of  a  fire  control  and  indicating  equipment  (unit),  is  powered  via  the  alarm  loop,  and  triggers fire 

alarms by increasing the loop current as a result of reducing its effective resistance. 
1.4

 

The  detector  is  powered  via  an  alarm  loop  of  a  control  and  indicating  equipment  (unit)  such  as  Signal-10,  S2000-4,  Signal-20P,  S2000-ASPT, 

Signal-20M, Signal-20, which provides loop voltage up to 30 V and limits the current in a loop at a level not exceeding 20 mA. The minimum powering 
voltage in the loop is to be 10 V. 
1.5

 

The detector is intended for round-the-clock operation and is classified as a repairable and periodically maintained item. 

1.6

 

The version of DIP-31 firmware is v.1.05. 

1.7

 

The detector can be tested using a System Sensor remote test unit, or Astra-942 Laser Tester from the TEKO Company, or OT-1 Optical Tester from 

the RUBEZH Company. 

2

 

SPECIFICATIONS 

2.1

 

Sensitivity, dB/m 

-

 

0.05 to 0.2 

2.2

 

Rated power voltage, V 

-

 

24  

2.3

 

Consumed current,  

 

-

 

In the quiescent mode, uA 

-

 

140 max 

-

 

In the fire alarm mode, mA 

-

 

10 max 

2.4

 

Internal resistance of the detector in the Fire Alarm mode at the current value: 

 

-

 

8 mA  

-

 

2.6 kOhm max; 

-

 

2 mA  

-

 

4.5 kOhm max 

2.5

 

Start-up time, s 

-

 

40 max 

2.6

 

Operating temperature range, °

С

 

-

 

Minus 10 t55 

2.7

 

Relative air humidity, % 

-

 

Up to 93 at +40 °

С

 

2.8

 

Enclosure protection degree 

-

 

IP40 

2.9

 

Overall dimensions, mm: 

 

-

 

Diameter 

-

 

100 max 

-

 

Height 

-

 

47 max 

2.10

 

 

Weight, kg 

-

 

0.1 max 

2.11

 

 

Alarm loop wire cross-section, sq. mm 

-

 

0.125 through 2.5 

2.12

 

 

Immunity to background illumination due to artificial and natural lighting, lux 

-

 

12,000 min 

2.13

 

 

Radio-frequency electromagnetic field immunity as per GOST R 51317.4.3–99 

-

 

Test severity level 3 

2.14

 

 

Immunity to electrostatic discharge as per GOST R 51317.4.2-99 

-

 

Test severity level 3 

2.15

 

 

Class of electric shock protection as per GOST 12.2.007.0-75 

-

 

III 

2.16

 

 

Air velocity at mounting location, m/s 

-

 

15 max 

2.17

 

 

MTBF, hours 

-

 

60,000 min 

2.18

 

 

Expected lifetime, years 

-

 

10 min 

Test Alarm Time specification, s: 

 

Test Fire Type 

Heat Release Rate 

Upward Flow 

Limit Value 

Actual Value 

TF2: Smouldering wood fire 

small 

weak 

840 

343 max 

TF3: Smouldering cotton fire 

small 

weak 

750 

215 max 

TF4: Flaming plastics fire 

high 

strong 

180 

115 max 

TF5: Flaming liquid (n-heptane fire) 

high 

strong 

240 

154 max 

3

 

STANDARD DELIVERY 

Item 

Quantity, pcs. 

Remark 

IP 212-31 DIP-31 Smoke Detector (body) 

10 

 

IP 212-31 DIP-31 Detector Base 

10 

 

Operations Manual 

 

Protective (Dust) Cover 

10 

 

Grouping Package 

 

VUOS-31 Remote Indicator 

10 

Ordered separately 

MK-2  or  MK-3  Recessed  Mounting  Kit  for  mounting  the  detector  onto  suspended 
ceiling 

10 

Ordered separately 

Summary of Contents for IP 212-31 DIP-31

Page 1: ...ensitivity dB m 0 05 to 0 2 2 2 Rated power voltage V 24 2 3 Consumed current In the quiescent mode uA 140 max In the fire alarm mode mA 10 max 2 4 Internal resistance of the detector in the Fire Alarm mode at the current value 8 mA 2 6 kOhm max 2 mA 4 5 kOhm max 2 5 Start up time s 40 max 2 6 Operating temperature range С Minus 10 through 55 2 7 Relative air humidity Up to 93 at 40 С 2 8 Enclosur...

Page 2: ... holes into the surface according to the drilling pattern in Figure 2 and attach the base by means of screws and wall plugs or tapping screws 5 2 To install the detector onto fire resistant tiles of suspended ceiling use MK 2 or MK 3 mounting kit for attaching the detector base Figure 3 Position 1 Make a mounting hole for the mounting kit according to the marking Figure 3 5 3 Until installation wo...

Page 3: ...ured levels of sensing chamber signal are 75 of the fire condition level FIRE ALARM Light steadily CONTAMINATED CHAMBER Three flashes every 6 s if the signal level has slowly reached 75 percent of the maximum contamination level Drift compensation is performed every 24 hours FAULT Four flashes spaced 200 ms apart every 6 s if the measuring function of the detector is out of order 7 TESTING 7 1 App...

Page 4: ...mitted to the following address NVP BOLID 4 Pionerskaya Str Korolyov Moscow Region 141070 Russia Tel fax 7 495 775 71 55 PBX E mail info bolid ru 8 7 In case of any issue related to use of the product please contact the technical support 7 495 775 71 55 or e mail support bolid ru 9 TRANSPORTING STORAGE DISPOSAL 9 1 The detectors in a transport container are to be transported by any type of covered...

Reviews: