background image

 

5.5

 

For installing the detector body, place it onto the base as shown in Figure 5 (

А

) and rotate clockwise until reaching into the guiding grooves. Then 

rotate it until rest as shown in Figure 5 (B). 
 

 

 

Figure 5 

 
5.6

 

For releasing the detector, insert the key (Figure 4, Position 3) into the slot (Figure 4, Position 4), push inward and in the same time rotate the detector 

body counterclockwise. Then remove the key from the slot and rotate the detector body further in the same direction until it is separated from the base. 
5.7

 

Mounting and dismounting can only be carried out with the equipment in de-energized state.  

6

 

WIRING 

6.1

 

The detectors, along with VUOS-31 remote indicators or without them, are electrically wired into the alarm loops of control and indicating equipment 

per the schematic shown in Figure 6.  

In  general  for  generating  events 

Fire Alarm 1

  (

Pre-Alarm

)  and 

Fire Alarm

  in  two-threshold  alarm  loops,  an  additional  resistor  is  to  be  brought  in 

series with the detector. DIP-31 have already had additional resistors built in within them, which facilitates mounting the detectors for their operation with 
fire control and indicating equipment (units) such as Signal-10, S2000-4, Signal-20P, S2000-ASPT, Signal-20

М

, Signal-20. 

6.2

 

While connecting the detectors into alarm loops of fire alarm and control units Signal-10, Signal-20P, S2000-4 and devices Signal-20M, S2000-ASPT 

as per Figure 6, the following types of alarm loops can be assigned: 

1: Fire Smoke (two-threshold);  
2: Fire Combined (single-threshold).  
For both cases the end resistor in a loop is Rt = 4.7K Ohm. 

6.3

 

The detector is protected against reverse polarity of connecting alarm loops. 

6.4

 

Wiring shall be carried out with the equipment in de-energized state. 

6.5

 

When connecting wires, it is advised to use cable shoes. 

 

Figure 6 

 

The detector provides indication of the following conditions by means of two red built-in visual indicators as follows:  
QUIESCENT CONDITIONS: Flashing once every 6 s;  
PREALARM: Two flashes every 6 s (when two successive measured levels of sensing chamber signal are 75% of the fire condition level); 
FIRE ALARM: Light steadily; 
CONTAMINATED CHAMBER: Three flashes every 6 s (if the signal level has slowly reached 75 percent of the maximum contamination level. Drift 
compensation is performed every 24 hours). 
FAULT: Four flashes spaced 200 ms apart every 6 s (if the measuring function of the detector is out of order). 

7

 

TESTING 

7.1

 

Apply power to the control and indicating equipment to which loop the detector is connected. The control and indicating equipment should be known 

good device. 
7.2

 

In the absence of smoke, the detector is in the quiescent conditions, red light emitting indicators flashing once per 6 s.  

7.3

 

To  check  the  detector  response,  present  the  can  with  aerosol  simulated  smoke  to  the  sensing  chamber  of  the  detector  and  release  a  single  burst  of 

smoke agent. Not later than 40 s after exposure to aerosol the detector shall go into the fire alarm conditions, the detector’s light emitting diodes starting to 
light steadily. The fire alarm shall be received and indicated by the control and indicating equipment. 

Note:

  

For testing smoke detectors you are advised to use aerosol smoke products such as Smokesabre 01-001, CHEK01-001, or similar. 

7.4

 

A more simplified functional test can be conducted by lighting one of the detector’s LEDs or the LED of the connected remote indicator VUOS-31 

with the laser beam of the remote test unit. The detector will go to the fire alarm conditions. The distance between the remote test unit and the illuminated 
LED shall be at least 0.5 m. 

Note:

  

A VUOS-31 remote indicator with the red LED (and colour free LED cap) is suitable for testing with a laser tester. Other remote 
indicators can be not suitable for this purpose.

 

7.5

 

If no fire alarm is registered by the control and indicating equipment, or light emitting indicators operate in a way which differs from the specified 

one, the detector is unhealthy and shall be replaced. 

W A R N I N G !  

Prior to testing the detector’s operability in an actual fire alarm system, disconnect outputs of the control and indicating equipment that control 
fixed fire suppression systems, voice announcement systems, general ventilation and smoke control systems. 

Summary of Contents for IP 212-31 DIP-31

Page 1: ...ensitivity dB m 0 05 to 0 2 2 2 Rated power voltage V 24 2 3 Consumed current In the quiescent mode uA 140 max In the fire alarm mode mA 10 max 2 4 Internal resistance of the detector in the Fire Alarm mode at the current value 8 mA 2 6 kOhm max 2 mA 4 5 kOhm max 2 5 Start up time s 40 max 2 6 Operating temperature range С Minus 10 through 55 2 7 Relative air humidity Up to 93 at 40 С 2 8 Enclosur...

Page 2: ... holes into the surface according to the drilling pattern in Figure 2 and attach the base by means of screws and wall plugs or tapping screws 5 2 To install the detector onto fire resistant tiles of suspended ceiling use MK 2 or MK 3 mounting kit for attaching the detector base Figure 3 Position 1 Make a mounting hole for the mounting kit according to the marking Figure 3 5 3 Until installation wo...

Page 3: ...ured levels of sensing chamber signal are 75 of the fire condition level FIRE ALARM Light steadily CONTAMINATED CHAMBER Three flashes every 6 s if the signal level has slowly reached 75 percent of the maximum contamination level Drift compensation is performed every 24 hours FAULT Four flashes spaced 200 ms apart every 6 s if the measuring function of the detector is out of order 7 TESTING 7 1 App...

Page 4: ...mitted to the following address NVP BOLID 4 Pionerskaya Str Korolyov Moscow Region 141070 Russia Tel fax 7 495 775 71 55 PBX E mail info bolid ru 8 7 In case of any issue related to use of the product please contact the technical support 7 495 775 71 55 or e mail support bolid ru 9 TRANSPORTING STORAGE DISPOSAL 9 1 The detectors in a transport container are to be transported by any type of covered...

Reviews: