BOGE Operating instructions for C 15 series screw compressors
Page 37
Installation
3.6
Dismantling
Fig. 3.7: Suction controller
3.6 Dismantling
–
Unscrew the plug on the suction
controller (1).
–
Fill approx. 0.03 gallons com-
pressor oil into the suction con-
troller.
–
Reclose the controller using the
plug.
–
Prior to switching on the com-
pressor wait for approx.10 min.
until the oil has spread evenly.
Then switch the compressor on
and immediately off again.
–
After approx.10 sec. the com-
pressor can be started.
NOTICE!
To avoid dangers when dismantling the compressor please consult your
BOGE Service:
Telephone: +1-770-874-1570
Telephone: +49 5206 601-140
WARNING!
Dismantling of the compressor may only be carried out by experienced and
authorized qualified personnel!
DANGER: Voltage!
All work on the electrical installation may only be carried out by authorized
and skilled electricians!
Prior to starting the work the power cable to the switch cabinet must be dis-
connected from the mains and secured against unintentional switching on!