Page 28
Flex-Pro
4.7
Remote/Local Control
The Flex-Pro can be configured for Remote control only, Local control only, or
either (disabled).
When set for Remote control only, all touch pad buttons except the menu button are
disabled. To completely lock out the menu, configure a password (see page 12,
section 8). If REMOTE ONLY is selected, the user is prompted to select an input
operating mode which must then be used when operating the pump.
When set for local control only, all input signals including the remote start/stop are
disabled. Note that the “contact closure input” menu setting (section 4.4) is
switched to “disabled” while
LOCAL ONLY
is selected. This menu setting will return
to the previous setting when
REMOTE ONLY
or
DISABLED
is selected.
- Input Setup
+ Input Modes
+ Contact Input
+ Set FVS
<- Esc
Hidden
+ Set Rev Alarm
+ Set TFD
+ Remote/Local
- Remote/Local
Remote Only
Local Only
Disable
Done
(select one)
- Remote Only Input Mode
4-20 mA
0-10 VDC
Frequency
(select one)
Hidden
Done
Proportional
Pulse
Removing the pump head
cover automatically puts
the pump into
“maintenance” mode,
allowing the operator to
replace the pump tube
without changing the
Remote/Local settings.
Tip!
MAINTENANCE MODE
Pump Cover Removed!
Press STOP to stop
- Cover was removed!
- Motor Speed = 6 RPM
MAINTENANCE MODE
Press START to run
4.8
Pump Tube Timer
Flex-Pro has a built in Pump Tube Timer. Timer starts when rotor is rotating and stops
when rotor is idle. To view current Pump Tube Timer value, press ENTER and DOWN
arrow at same time while in the normal operating mode.
Screen will display current Pump Tube Time in run-time hours. While displayed, press
ENTER button twice to reset Pump Tube Timer to zero.
+
186
PUMP TUBE TIMER
Enter twice to reset
Current tube timer:
Hrs.