Voltage

Voltage at motor

MUST NOT

be more than 10% above or below motor name plate rated voltage, or motor may

overheat, causing overload tripping and reduced component life. If voltage is less than 90% or more than 110% of
rated voltage when motor is running at full load, consult Power Company.

Grounding and Bonding

Install, ground, bond, and wire motor in accordance with local or national electrical code requirements.
Permanently ground motor. Use green ground terminal provided under motor canopy or access place; use size and
type wire required by code. Connect motor ground terminal to electrical service ground. Bond motor to pool
structure. Bonding will connect all metal parts within and around the pool with a continuous wire.
Bonding reduces the risk of a current passing between bonded metal objects, which could potentially cause
electrical shock if grounded or shorted.

Reference NEC codes for all wiring standards including, but not

limited to, grounding, bonding and general wiring procedures.

Use a solid copper conductor, size 8 or larger. Run wire from external bonding lug to reinforcing rod or mesh.
Connect a No. 8 AWG (8.4 mm

2

) solid copper bonding wire to the pressure wire connector provided on the motor

housing and to all metal parts of swimming pool, spa, or hot tub, and to all electrical equipment, metal piping
(except gas piping), and conduit within 5 ft. (1.5 m) of inside walls of swimming pool, spa, or hot tub.

Wiring

WARNING –

All wiring must be done by a licensed electrician.

Pump MUST be permanently connected to circuit. If other lights or appliances are also on the same circuit, be sure
to add their amp loads before calculating wire and circuit breaker sizes. Use the load circuit breaker as the Master
On-Off switch.
Install a Ground Fault Circuit Interrupter (GFCI) in circuit; it will sense a short-circuit to ground and disconnect
power before it becomes dangerous to pool users. For size of GFCI required and test procedures for GFCI, see
manufacturer’s instructions. In case of a power outage, check GFCI for tripping, which will prevent normal pump
operation. Reset if necessary.

NOTE - If you do not use conduit when wiring motor, be sure to seal wire opening on end of motor to
prevent dirt, bugs, etc., from entering.

Start-Up & Operation

Prior to Start-Up

Notice: If it is necessary to perform a pressure test, prior to initial use to ensure pump is functioning properly, then
the following criteria should be maintained for this test:
1. Have a professional perform this test.
2. Ensure all pump and system components are sealed properly to prevent leaks.
3. Remove any trapped air in the system by fully opening filter manual air relief valve until a steady stream of
water is discharged.
4. Allow no more than 40 psi (276 kPa) at a water temperature no higher than 10

o

o

0 F (38 C).

5. Run pressure test for no longer than 24 hours. Immediately inspect all parts to verify they are intact and
functioning properly.

page 7

Summary of Contents for Flow Xtreme NE4513

Page 1: ...REPLACEMENT PUMPS OWNER S MANUAL INSTALLATION OPERATION PARTS NE4513 NE4515 NEP4208 NE4514 NE4516 NE4517 NE4520 NE4518 NE4521 NE4519 NE4522 NE4523 NEP4268 NEP4269 VER 0611 NE4524 NEP4271...

Page 2: ...so that it is capable of being readily disassembled for storage and reassembled to its original integrity Though this product is designed for outdoor use it is strongly advised to protect the electri...

Page 3: ...tion outlets and or suction outlet covers which are damaged broken cracked missing or unsecured can cause severe injury and or death due to the following entrapment hazards Hair Entrapment Hair can be...

Page 4: ...nd water is discharged All suction and discharge valves MUST be OPEN when starting the circulation system Failure to do so could result in severe personal injury and or property damage WARNING Separat...

Page 5: ...Allow adequate access for servicing pump and piping Pipe Sizing Chart NOTE It is recommended that a minimum length of piping MAXIMUM RECOMMENDED SYSTEM FLOW RATE BY PIPE SIZE Pipe Size mm 1 32 1 1 4 4...

Page 6: ...electrical shock hazard WARNING Do NOT ground to a gas supply line WARNING To avoid dangerous or fatal electrical shock turn OFF power to motor before working on electrical connections WARNING Ground...

Page 7: ...5 ft 1 5 m of inside walls of swimming pool spa or hot tub Wiring WARNING All wiring must be done by a licensed electrician Pump MUST be permanently connected to circuit If other lights or appliances...

Page 8: ...t in severe personal injury Release all pressure from filter pump and piping system See filter owner s manual If water source is higher than the pump pump will prime itself when suction and outlet val...

Page 9: ...in the system Drain all water from pump and piping when expecting freezing temperatures or when storing pump for a long time see instructions below Keep motor dry and covered during storage To avoid...

Page 10: ...r power drop frequently caused by undersized wiring or extension cord use Solution Contact qualified professional to check that the wiring gauge is heavy enough NOTE Your pump motor is equipped with a...

Page 11: ...seal only if it is leaking Low Flow Generally Check For 1 Clogged or restricted strainer or suction line Solution Contact a qualified repair professional 2 Undersized pool piping Solution Correct pip...

Page 12: ...tz Amps Flow Rate NE4517 HTI100 1 0 115 230 60 13 6 5 86GPM NE4518 HTI150 1 5 115 230 60 15 7 5 90GPM NE4519 HTI2SP075 0 75 0 23 230 60 6 80 35GPM NE4520 HTI2SP100 1 0 0 3 230 60 1 6 1 8 86 38GPM NE45...

Page 13: ...19 8 IMPELLER OF ITEM HTI 100 HTI2SP 100 HTI010 NEP4218 NE4517 NE4520 8 IMPELLER OF ITEM HTI 150 HTI2SP 150 HTI011 NEP4219 NE4518 NE4521 8 IMPELLER OF ITEM HTI 200 HTI2SP 200 HTI012 NEP4220 NE4522 9 O...

Page 14: ...4 All 9 PUMP COVER HTA011 NEP4195 All 10 O RING HTA012 NEP4196 All 11 IMPELLER OF ITEM HTA 075 HTA2SP 075 HTA014 NEP4198 NE4513 NE4515 IMPELLER OF ITEM HTA 100 HTA2SP 100 HTA015 NEP4199 NE4514 NE4516...

Page 15: ...5 43 O ring B 3 1 P00183 NEP4266 All 6 44 O ring C 1 5 1 P00184 NEP4267 All 7 45 Strainer Collar 1 P00133 NEP4247 All 8 46 Strainer Basket 1 P00134 NEP4248 All 9 47 Pump Drain Cap 1 P00135 NEP4249 All...

Reviews: