Gas Conversion and Specifications
Gas Regulator
NOTE: The regulator supplied is convertible between Natural Gas and LPG, but it’s outlet
pressure is fixed ex-factory and is NOT to be adjusted.
1.
Ensure that the gas supply is turned ‘OFF’ at the mains.
2.
Unscrew the hexagonal cap (23mm A/F) from the regulator.
3.
Un-clip the plastic pin from the cap, rotate the pin and re-fit it back to
the cap the correct way for the gas type to be used.
(Either ‘LP’ or
‘NAT’ should be visible on the flank of the pin once
re-fitted to the cap)
.
4.
Screw the cap back into the regulator.
Gas Type Identification Label
On completion of the gas conversion, replace the gas type identification label, located at the rear of the
unit, above the gas entry port.
Low Fire Adjustment
The gas control valve is fitted with a maximum flow bypass blanking screw.
No adjustment is required
.
NOTE, Pin rotated
for Natural Gas
NOTE, Pin
rotated for LPG
Fig 9