1
Model BB4000 Controller Instruction Manual
1. I
ntroductIon
1.1. Applications
Simplex, Duplex, Triplex, or Quadraplex
Liquid Level Control
Pump Down (Empty a Tank) or Pump Up (Fill
a Tank)
Fixed or Variable Speed Control
Where Connection to a SCADA System is
Required
1.2. Standard Features
All Setup Parameters Values may be viewed or
changed from the front of the unit.
Level Input Source - Menu Selectable:
–
Analog Level Input [4-20mA from
Pressure Transducer]
–
Level Probe [Conductance Probe with
10 Electrodes]
Reg20Vdc power for Analog Level
Input
RS-232 Serial Port with Modbus RTU Protocol
High and Low Level Alarm Relays and Alarm
Indication
Adjustable lag Pump(s) Delay
Alternation Schemes - Menu Selectable:
–
Standard Alternation
–
Pump 1 Always Lead - Stays On with
other Pumps
–
Pump 1 Always Lead - Turns Off with
other Pumps On
–
Split Alternation - Pumps 1&2, and
Pumps 3&4
–
Fixed Sequence - Pump 1 Always Lead
–
Stepped On/Off - Only One Pump
Runs at a Time
Alternator Logic Skips Disabled Pumps
First On - First Off or First On - Last Off
Alternation
Level Simulation (Automatically ends after 1
minute)
Security Code Protected Parameter Setup
18 Discrete Inputs programmable for the
following functions:
–
Pump disable with HOA in OFF, or
pump fault
–
External Lead Pump Selector Switch
–
All pump disable - for connection to
Phase Monitor
–
Limit number of pumps called while on
emergency power
–
Alternation by External Time Clock
–
Freeze wet well level during a bubbler
tube purge
–
Call pump last
–
Float switch backup
–
Low Level Pump Cutoff
–
Start Flush Cycle
–
A variety of SCADA functions
Status of Discrete Inputs may be viewed from
front of Controller
Backup Control, and High & Low Alarms using
a Level Probe
Output Relays may be programmed for control
through SCADA
Automatic Flush Cycle to reduce sludge build up
Flow Calculator that provides the following Flow
Data:
–
Latest Inflow Rate
–
Average Daily Inflow Total (Average of Last
7 Days)
–
Pump Outflow Rate (Latest for Each Pump)
1.3. Optional Features
Up to four Isolated 4-20mA Analog Outputs
that may be used for VFD speed control or for
sending out a copy of the Level Input
Up to four Isolated 4-20mA Auxiliary Analog
Inputs that may be used to collect analog data
for SCADA
4-20mA Analog Level Input may be ordered as
an Isolated Input
Ethernet Port with the following Protocols:
Modbus TCP or Modbus RTU
1.4.
Specifications
Input Power: 120 VAC ±10%, 13 VA max
External Dimensions: 6.9”x 8.5”x 4.9”
Agency Approvals: UL 508, CAN/CSA
Ambient Operating Temperature:
Without Analog Outputs:
-20 °C to +65 °C (-4 °F to +149 °F)
With Analog Outputs:
-20 °C to +50 °C (-4 °F to +122 °F)
Level Display: 3 Digit, 7 Segment LED