28
Model BB4000 Controller Instruction Manual
4. Use the Up / Down push-buttons to make the display read the level (in feet of water)
that your 20mA signal represents. Note: It is slow to change at first.
(Alternate Procedure - Use the Up / Down push-buttons t make the display read the
number of feet of water that the pressure transducer or the end of the bubbler tube is
submerged under.
5. Repeat the procedure above for the “LEVEL INPUT ZERO” Parameter.
10.3. Level Display Span VS. Transducer Calibration
t
ranSDucer
c
alibration
4.33 PSI
@ 20mA
5.0 PSI
@ 20mA
10 PSI
@ 20mA
15 PSI
@ 20mA
30 PSI
@ 20mA
60 PSI
@ 20mA
100 PSI
@ 20mA
LEVEL
DISPLAY
SPAN
-
-
-
-
-
139 feet
231 feet
P.36 = 0
-
11.5 feet
23.1 feet
34.6 feet
69.3 feet
-
-
P.36 = 1
9.99 feet
-
-
-
-
-
-
P.36 = 2
Notes:
1. Level Display Span is what is displayed with a 20mA Level Input.
2. Parameter P.36 is used to set the decimal point position.
3. To find the Level Input Span Setting for other transducers, use the following equation:
Pressure (PSI) x 2.309 = Level (feet of water)