Model BB4000 Controller Instruction Manual
16. e
thernet
p
ort
- o
ptIon
16.1. Features
The Ethernet Port has the following features:
Protocols Supported: Modbus TCP or Modbus RTU
IEEE 802.3 Compliant
100 Mbps communication speed
Full-Duplex operation
Link, and Active status LED indicators
leD i
nDicator
off
on
LINK (Green)
Not Linked
Linked
ACTIVE (Yellow)
Idle
Active Communication
16.2. Setup of Ethernet Port
p
araMeter
D
efault
V
alue
c
urrent
V
alue
p
araMeter
D
efinitionS
E.01
2
Protocol
1 = Modbus RTU 2 = Modbus TCP
E.14 - E.11
192 . 168 . 80 . 12
(E.14 . E.13 . E.12 . E.11)
IP Address Range: 0 - 255
Identifier for the device on an IP network.
E.44 - E.41
255 . 255 . 255 . 0
(E.44 . E.43 . E.42 . E.41)
Subnet Mask Range: 0 - 255
Range of IP addresses that can be Directly connected in the
network.
E.54 - E.51
192 . 168 . 80 . 1
(E.54 . E.53 . E.52 . E.51)
Default Gateway Range: 0 - 255
A node on the network that serves as an entrance to another
network when no direct connection exists.
E.62 - E.61
0
,
502
(E.62
,
E.61)
Port Number Range: 1 - 65,535
Note:
The Ethernet Port reads the setup values upon power up; any changes require the power to be cycled
before the new values are used.
p
araMeter
f
ixeD
V
alue
p
araMeter
D
efinition
E.36 - E.31
0 : 80 : 194 : 219 : XXX : XXX
(E.36 : E.35 : E.34 : E.33 : E.32 : E.31)
MAC Address
Unique number that identifies each field device.
It is set at the factory, and cannot be change.