Model BB4000 Controller Instruction Manual
4. M
enu
- d
ata
d
Isplay
P
arameter
D
ata
D
eSCriPtion
L.01
Electrode 1 Status Value
Level Probe Electrode Status Values
Normal Range when Un-Covered: 240 - 255
Normal Range when Covered by Typical Sewage: 55 - 70
Notes:
1. The Controller compares each of the Electrode Status Values with what is set on Para-
meter F.22. When the value drops below the setting on Parameter F.22, the Controller
logic considers the Electrode to be covered by liquid.
2. Parameters L.01 - L.10 are also used to diagnose Out of Sequence Faults (Fault Codes
21 - 29).
3. For the status of the Level Probe inputs see Coils 583 - 592 in SCADA Register 40037.
L.02
Electrode 2 Status Value
L.03
Electrode 3 Status Value
L.04
Electrode 4 Status Value
L.05
Electrode 5 Status Value
L.06
Electrode 6 Status Value
L.07
Electrode 7 Status Value
L.08
Electrode 8 Status Value
L.09
Electrode 9 Status Value
L.10
Electrode 10 Status Value
L.11
Level Probe Test Signal Status Normal Range: 230 -254
Note: This is a Measure of the
±
8v, 60 Hz Square Wave Sent Out to Each Electrode to read the level. If the value is below 210, a
malfunction has occurred in the circuit that provides the Square Wave used to read the level. In this case, the wet well level display
will show zero, the Fault indicator will be turned on, and Fault Code 20 will be generated.
FLH
Flow Calculator - Latest Inflow Rate
See pages 32 - 35.
FLH, FLL Gallons Per Minute
SCADA Register 40080
FLL
FdH
Flow Calculator - Average Daily Inflow Total
See pages 32 - 35.
FdH, FdL Units set by Parameter P.45.
SCADA Register 40081
FdL
F1H
Flow Calculator - Pump 1 Outflow Rate
See pages 32 - 35.
F1H, F1L Gallons Per Minute
SCADA Register 40082
F1L
F2H
Flow Calculator - Pump 2 Outflow Rate
See pages 32 - 35.
F2H, F2L Gallons Per Minute
SCADA Register 40083
F2L
F3H
Flow Calculator - Pump 3 Outflow Rate
See pages 32 - 35.
F3H, F3L Gallons Per Minute
SCADA Register 40084
F3L
F4H
Flow Calculator - Pump 4 Outflow Rate
See pages 32 - 35.
F4H, F4L Gallons Per Minute
SCADA Register 40085
F4L