Installation
9
Ventilation
DIRECT FLUE ARRANGEMENT
When the installation of a mechanically driven ex-
haust hood is impractical the oven may be vented
by a direct flue arrangement.
WARNING!!
It is essential that the direct flue be
installed as follows. Incorrect installation
will result in unsatisfactory baking and
oven damage.
The flue must be class B or better. The height of
the flue should rise 6-8 ft (2-2.5 m) above the roof
of the building or any proximate structure. Never
direct vent the oven into a hood. The flue should
be capped with a UL Listed type vent cap to isolate
the unit from external environmental conditions.
The direct vent cannot replace air consumed and
vented by the oven. Provisions must be made to
supply the room with sufficient make-up air. Total
make-up air requirements for each oven section
should be approximately 30 CFM (.85 m
3
) per sec-
tion. To increase the supply air entering the room,
a ventilation expert should be consulted.
FLUE DIAMETER
Oven
Single
Double
SHO-G
6” (15cm)
6” (15cm)
Installing the draft hood
Ovens ordered for direct venting are supplied with
a draft hood. Install the draft hood as follows:
1. Place the draft hood over the flue connector.
See Figure 9.
2. Secure both ends with the sheet metal screws
provided.
Front of
Oven
Draft Hood
Flue
Figure 9