87
E
N
G
L
IS
H
Settings
Display menu
(choice of parameter to be displayed during operation, view the last
fault, speed controller software version and access code)
The display chosen is saved by :
- Pressing the ENT key once: the choice is temporary, it will be cleared at the next power up.
- Pressing the ENT key twice : the choice is permanent. The second press on ENT exits the SUP- menu.
The following parameters can be accessed, with the speed controller stopped or running.
Code
Parameter
Unit
-FrH
Display the frequency reference
Hz
-rFr
Display the output frequency applied to the motor
Hz
-SPd
Display the value calculated by the speed controller (rFr x SdS)
–
-LCr
Display the motor current
A
-OPr
Display the power supplied by the motor, estimated by the speed controller.
100 % corresponds to the nominal speed controller power.
%
-ULn
Display the line voltage
V
-tHr
Display the motor thermal state : 100% corresponds to the nominal thermal state.
Above 118%, the speed controller triggers an OLF fault (motor overload)
%
-tHd
Display the speed controller thermal state : 100% corresponds to the nominal thermal state.
Above 118%, the speed controller triggers an OHF fault (drive overheated)
It can be reset below 70%.
%
-LFt
View the last fault which appeared. If there has been no fault, the display shows : noF.
–
-CPU
Speed controller software version
–
-COd
Parameter which can only be seen and accessed using a remote display module option or PC software.
Access code : 0 to 9999. Value 0 (factory setting) does not prevent access. All other values lock access
to the SEt-, drC- and I-O- menus.
To lock access to the speed controller, the code can be incremented using (
s t
) then saved using (ENT).
• Do not forget to make a note of the code, as once it has been saved, it is no longer
displayed.
• If a code other than 0 is configured, access to the menus requires a remote
display module option or PC software.
To access the menus on a speed controller which is locked by a code, the code can be incremented using
(
s t
) and confirmed with (ENT) :
• If the correct access code is displayed, it flashes, and code 0 can then be configured in order to access
the menus.
• If an incorrect code is displayed, the speed controller returns to the initial display (rdY).
SUP-