Settings
Adjust menu
(continued)
(1) In is the nominal speed controller current shown in the catalogue and on the speed controller rating
plate.
Code
Assignment
Adjustment
range
Factory
setting
-UFr
Optimizes the torque at very low speed
0 to 100 %
20
-SLP
Adjusts the slip compensation around the value set by the nominal motor
speed. This parameter only appears if parameter UFt = n in the drC- menu.
0.0 to 5.0 Hz
According
to controller
output
-FLG
Frequency loop gain
Linked to the inertia and the resistive torque of the driven mechanism :
- machines with high resistive torque or high inertia : gradually reduce the
gain in the range 33 to 0
- machines with fast cycles, low resistive torque and low inertia : gradually
increase the gain in the range 33 to 100. Too high a gain may result in
operating instability.
0 to 100 %
33
-IdC
Level of DC injection braking current
After 5 seconds the injection current is peak limited at 0.5 Ith if it is set at a
higher value.
0.1 ItH to
In (1)
0.7 In (1)
-tdC
DC injection standstill braking time
If the time is increased to 25.5 s, "Cont" is displayed. The DC injection is then
continuous at standstill.
0 to 25,4 s
Cont.
0.5 s
-JPF
Skip frequency prevents prolonged operation at a frequency range of 2 Hz
around JPF. This function prevents a critical speed which leads to resonance.
Setting the function to 0 renders it inactive.
0 to HSP
0 Hz
-JOG
Jog operating frequency
0 to 10 Hz
10 Hz
-rPG
PI regulator proportional gain
0,01 to 100
1
-rIG
PI regulator integral gain
0.01 to 100 / s 1 / s
-FbS
PI feedback multiplication coefficient
0.1 to 100
1
-PIC
Reversal of the direction of correction of the PI regulator :
no : normal, YES : reverse
no - YES
no
The parameters in shaded boxes appear if the corresponding functions have been configured
in the drC- or I-O- menus.
SEt-