Local control option
This option consists of a reference potentiometer and provides access to 2 additional buttons on the
speed controller (see documentation provided with the option) :
–
RUN button : controls the switching on of the motor. The direction of operation is determined by
parameter rOt in the settings menu SEt-.
–
STOP/RESET button : controls the stopping of the motor and the clearing (resetting) of any
faults The first press on the button stops the motor, and if DC injection standstill braking
is configured, a second press stops this braking.
The reference given by the reference potentiometer is summed with analog input AI1.
Installing this option requires special factory setting of certain functions :
• I/O :
-tCC = OPt
not reassignable
-LI1 = no
not reassignable
-LI2 = PS2
reassignable
-LI3 = PS4
reassignable
-LI4 = PS8
reassignable
• Drive : Atr = no, only reassignable at YES
This option cannot be removed once it has been fitted.
The option must be connected with the speed controller powered down, otherwise it will trip on an InF
fault.