TxxxES-E MODELS ONLY 

Parameter 

Description 

Material of body 

brass, nickel plated steel with plastic cover 

Switch point 

set to 1 bar (14 psi) 

Switch configuration 

NC 

Maximum pressure 

30 bar (435 psi) 

Max Power rating DC 
Max Power rating AC 

50/60 Hz 

36 V DC 

240 V AC 

3 A 

Electrical outlet 

2 x wire 0.75 mm

2

, 150 mm length 

IP rating 

IP54 

Operation temperature 

from -20 °C up to 80 °C (-4 °F to 176 °F) 

Tested to 

EN60730 - automatic electrical controls for household and similar use 

Advantages 

light weight, cost-effective 

 
 
 
 

 

 

 
 

 

 
MAINTENANCE 

 

The BlazeCut T Series does not require any special maintenance. It is recommended to visually inspect the 
system and its state at operating temperature, between every month and three months dependent on the type 
of environment it has been installed in. During the movement of the tube, bubbles of gas in the extinguishing 
agent will be visible. This indicates that extinguishing agent is in the tube and the BlazeCut T Series is functional. 

 
SYSTEM PRESSURE INSPECTION

 

 

It is recommended to inspect the pressure of the tube when the equipment is at operating temperature. Due to 
physical  and  chemical  properties  of  the  agent,  pressure  in  the  tube  can  vary  depending  on  the  ambient 
temperature. The higher the ambient temperature, the higher pressure in the tube and vice versa. 
 

IMPORTANT! At very low temperatures the pressure of agent vapours is close to zero. 
 

Indicator on the pressure gauge can vary from 0 bar (0 psi) when temperatures are very low to 17 bar (247 psi) 
when temperatures are very high. This is not a sign of defect in the system. 

 

CASES WHEN THE BLAZECUT SYSTEM MUST BE REPLACED

 

 

 

The system is leaking, was used or emptied from other reason. 

 

The system was exposed to direct fire. 

 

The tube shows signs of damage. 

 

Metal parts of the enclosure are corroded or show visible signs of damage. 

 

 
INSTRUCTIONS FOR PROCEDURE AFTER SYSTEM ACTIVATION

 

 

Extinguishing agent does not leave residue. Ventilate the protected enclosure properly, do not enter the area 
before  ventilation.  Remove  the  used  system  from  the  protected  enclosure.  The  same  procedure  should  be 
followed after the release of extinguishing agent from other reasons (system damage etc.). 
In case of fire the system activates automatically burning the tube without previous warning. In case of fire do 
not come into direct proximity of the system, there is a risk of being affected by the extinguishing agent. 
In  case  of  activation  of  the  system  do  not  enter  the  protected  enclosure  and  do  not  open  the  covers  of  the 
protected enclosure, wait for total release of extinguishing agent. 

Pressure Switch models TxxxES-E 

When supplied before actuation 
(pressurized)

 

This is the configuration of the  Economy 
Pressure Switch  on models TxxxES-E 
 

Summary of Contents for T Series

Page 1: ...FULLY This user manual contains important information about the BlazeCut T Series fire suppression system its use operation installation and maintenance If further technical information is required please request a copy of the T Series technical manual from a BlazeCut representative ...

Page 2: ...tely Following skin contact Flush irrigate the affected area with large amount of water Do not use hot water Remove contaminated clothing affected by extinguishing agent If you experience frostbite seek medical attention Following eye contact Carefully flush irrigate with water for several minutes If possible remove contact lenses if they are inserted Continue flushing Seek medical attention Follo...

Page 3: ...into one unit The BlazeCut T Series is not compatible with other fire suppression systems do not try to connect the system to any other equipment The system may be installed only by adult persons physically and mentally capable Incorrect interference with the system may cause malfunction of the system and provides threat to safety and health of people The system is under constant pressure any mech...

Page 4: ...18 ft3 0 11 lb 0 07 oz 11 02 in T050E 0 18 m3 0 14 m3 0 10 kg 2 g 53 cm 6 36 ft3 4 94 ft3 0 22 lb 0 07 oz 20 87 in T100E 0 46 m3 0 35 m3 0 25 kg 5 g 113 cm 16 24 ft3 12 36 ft3 0 55 lb 0 17 oz 44 48 in T200E 0 91 m3 0 69 m3 0 50 kg 5 g 215 cm 32 14 ft3 24 37 ft3 1 10 lb 0 17 oz 84 64 in T300E 1 37 m3 1 04 m3 0 75 kg 10 g 319 cm 48 38 ft3 36 73 ft3 1 65 lb 0 35 oz 125 59 in T400E 1 82 m3 1 39 m3 1 0...

Page 5: ...oisonous unnecessary excessive exposure of persons to its influence should be avoided Under no circumstances should persons be exposed to the extinguishing agent for more than 5 minutes also in case when the extinguishing concentration does not exceed the LOAEL level contact your local BlazeCut supplier for more information During the system activation the extinguishing agent is discharged from th...

Page 6: ... with the letter S in model designation have an integrated pressure switch that allows connection of signalling devices or to perform a shutdown operation at agent discharge An IP65 Pressure Switch is factory fitted for outdoor and mobile applications T Series models with the letters S E in model designation have an integrated economy pressure switch that allows connection of signalling devices or...

Page 7: ...ishing effect of the system may be decreased and part or the entire protected enclosure may be damaged 11 Install the system so that it is not exposed to aggressive chemical substances caustic acids solvents corrosive substances etc and avoid direct influence of weather conditions and direct sunlight 12 When fastening the system make sure not to damage other parts of the vehicle or the enclosure 1...

Page 8: ...100 min 1 Maximum pressure 60 bar 870 psi Power rating Angular connector All Current Resistive load AC 12 DC12 AC 250 V DC 24 V 4 A Inductive load AC 14 DC14 AC 250 V DC 24 V 2 A IP rating IP65 with cable connector and seal Electrical outlet DIN EN 175301 803 A Operation temperature from 20 C up to 80 C 4 F to 176 F Tested to EN60947 Low voltage switchgear and control gear IEC 68 2 78 Permissible ...

Page 9: ...er pressure in the tube and vice versa IMPORTANT At very low temperatures the pressure of agent vapours is close to zero Indicator on the pressure gauge can vary from 0 bar 0 psi when temperatures are very low to 17 bar 247 psi when temperatures are very high This is not a sign of defect in the system CASES WHEN THE BLAZECUT SYSTEM MUST BE REPLACED The system is leaking was used or emptied from ot...

Page 10: ... waste NEED SOMETHING MORE If there is a requirement for electronic monitoring external alarm or other size of system these are available Please contact technical blazecutgroup com GLOBAL HEAD OFFICE BlazeCut Pty Ltd 45 Evans St Balmain NSW 2041 Australia Tel 61 2 8006 1300 MANUFACTURER BlazeCut s r o Priemyselná 2521 90027 Bernolákovo Slovakia www blazecut com technical blazecutgroup com BlazeCut...

Reviews: