Extinguishing agent: 

HFC-227ea 

Tube diameter: 

 

19 mm (0.75 in) 

Operation temperature: 

90 °C (194 °F) maximum for TxxxE models 

 

 

 

80 °C (176 °F) maximum for TxxxES models 

Activation temperature: 

105 °C ± 3 °C (221 °F ± 5 °F) for TxxxE models 

 

 

 

100 °C ± 2 °C (212 °F ± 4 °F) for TxxxES and TxxxES-E models 

Activation pressure:  

24 bar ± 1 bar (348 psi ± 14 psi) for TxxxE models 

 

 

 

25 bar ± 1 bar (363 psi ± 14 psi) for TxxxES and TxxxES-E models 

Minimum bending radius: 

160 mm (6.30 in) 

 

SIZING AND SELECTION 

 
With vehicle applications please refer to our vehicle application list instore or visit 

www.blazecut.com 

Other applications can be calculated by a simple process: 

Measure the enclosures Width x Height x Depth in metres or feet and this will calculate your m

or ft

3

Note: the enclosure should be enclosed or have minimal vents. T series is not suitable for open areas. 

 

Then refer to the chart below to select the suitable length. 
 
T Series Standard & Pressure Switch Models (Vehicles & Enclosures) 
 

Model* 

Volume protected at 

20 °C (68 °F) 

Volume protected at 

20 °C (68 °F) 

Amount of agent 

System 

length 

Electrical Fires** 

Engine Fires** 

T025E 

0.09 m

3

 

0.09 m

3

 

0.05 kg ± 2 g 

28 cm 

(3.18 ft

3

(3.18 ft

3

(0.11 lb ± 0.07 oz) 

(11.02 in) 

T050E 

0.18 m

3

 

0.14 m

3

 

0.10 kg ± 2 g 

53 cm 

(6.36 ft

3

(4.94 ft

3

(0.22 lb ± 0.07 oz) 

(20.87 in) 

T100E 

0.46 m

3

 

0.35 m

3

 

0.25 kg ± 5 g 

113 cm 

(16.24 ft

3

(12.36 ft

3

(0.55 lb ± 0.17 oz) 

(44.48 in) 

T200E 

0.91 m

3

 

0.69 m

3

 

0.50 kg ± 5 g 

215 cm 

(32.14 ft

3

(24.37 ft

3

(1.10 lb ± 0.17 oz) 

(84.64 in) 

T300E 

1.37 m

3

 

1.04 m

3

 

0.75 kg ± 10 g 

319 cm 

(48.38 ft

3

(36.73 ft

3

(1.65 lb ± 0.35 oz) 

(125.59 in) 

T400E 

1.82 m

3

 

1.39 m

3

 

1.00 kg ± 10 g 

422 cm 

(64.27 ft

3

(49.09 ft

3

(2.20 lb ± 0.35 oz) 

(166.14 in) 

T500E 

2.28 m

3

 

1.73 m

3

 

1.25 kg ± 10 g 

526 cm 

(80.52 ft

3

(61.09 ft

3

(2.76 lb ± 0.35 oz) 

(207.09 in) 

T600E 

2.73 m

3

 

2.08 m

3

 

1.50 kg ± 10 g 

630 cm 

(96.41 ft

3

(73.45 ft

3

(3.31 lb ± 0.35 oz) 

(248.03 in) 

T025ES 

0.09 m

3

 

0.09 m

3

 

0.05 kg ± 2 g 

35 cm 

(3.18 ft

3

(3.18 ft

3

(0.11 lb ± 0.07 oz) 

(13.78 in) 

T050ES 

0.18 m

3

 

0.14 m

3

 

0.10 kg ± 2 g 

60 cm 

(6.36 ft

3

(4.94 ft

3

(0.22 lb ± 0.07 oz) 

(23.62 in) 

T100ES 

0.46 m

3

 

0.35 m

3

 

0.25 kg ± 5 g 

120 cm 

(16.24 ft

3

(12.36 ft

3

(0.55 lb ± 0.17 oz) 

(47.24 in) 

T200ES 

0.91 m

3

 

0.69 m

3

 

0.50 kg ± 5 g 

222 cm 

(32.14 ft

3

(24.37 ft

3

(1.10 lb ± 0.17 oz) 

(87.40 in) 

T300ES 

1.37 m

3

 

1.04 m

3

 

0.75 kg ± 10 g 

326 cm 

(48.38 ft

3

(36.73 ft

3

(1.65 lb ± 0.35 oz) 

(128.34 in) 

T400ES 

1.82 m

3

 

1.39 m

3

 

1.00 kg ± 10 g 

429 cm 

(64.27 ft

3

(49.09 ft

3

(2.20 lb ± 0.35 oz) 

(168.89 in) 

T500ES 

2.28 m

3

 

1.73 m

3

 

1.25 kg ± 10 g 

533 cm 

(80.52 ft

3

(61.09 ft

3

(2.76 lb ± 0.35 oz) 

(209.84 in) 

T600ES 

2.73 m

3

 

2.08 m

3

 

1.50 kg ± 10 g 

637 cm 

(96.41 ft

3

(73.45 ft

3

(3.31 lb ± 0.35 oz) 

(250.79 in) 

 

Summary of Contents for T Series

Page 1: ...FULLY This user manual contains important information about the BlazeCut T Series fire suppression system its use operation installation and maintenance If further technical information is required please request a copy of the T Series technical manual from a BlazeCut representative ...

Page 2: ...tely Following skin contact Flush irrigate the affected area with large amount of water Do not use hot water Remove contaminated clothing affected by extinguishing agent If you experience frostbite seek medical attention Following eye contact Carefully flush irrigate with water for several minutes If possible remove contact lenses if they are inserted Continue flushing Seek medical attention Follo...

Page 3: ...into one unit The BlazeCut T Series is not compatible with other fire suppression systems do not try to connect the system to any other equipment The system may be installed only by adult persons physically and mentally capable Incorrect interference with the system may cause malfunction of the system and provides threat to safety and health of people The system is under constant pressure any mech...

Page 4: ...18 ft3 0 11 lb 0 07 oz 11 02 in T050E 0 18 m3 0 14 m3 0 10 kg 2 g 53 cm 6 36 ft3 4 94 ft3 0 22 lb 0 07 oz 20 87 in T100E 0 46 m3 0 35 m3 0 25 kg 5 g 113 cm 16 24 ft3 12 36 ft3 0 55 lb 0 17 oz 44 48 in T200E 0 91 m3 0 69 m3 0 50 kg 5 g 215 cm 32 14 ft3 24 37 ft3 1 10 lb 0 17 oz 84 64 in T300E 1 37 m3 1 04 m3 0 75 kg 10 g 319 cm 48 38 ft3 36 73 ft3 1 65 lb 0 35 oz 125 59 in T400E 1 82 m3 1 39 m3 1 0...

Page 5: ...oisonous unnecessary excessive exposure of persons to its influence should be avoided Under no circumstances should persons be exposed to the extinguishing agent for more than 5 minutes also in case when the extinguishing concentration does not exceed the LOAEL level contact your local BlazeCut supplier for more information During the system activation the extinguishing agent is discharged from th...

Page 6: ... with the letter S in model designation have an integrated pressure switch that allows connection of signalling devices or to perform a shutdown operation at agent discharge An IP65 Pressure Switch is factory fitted for outdoor and mobile applications T Series models with the letters S E in model designation have an integrated economy pressure switch that allows connection of signalling devices or...

Page 7: ...ishing effect of the system may be decreased and part or the entire protected enclosure may be damaged 11 Install the system so that it is not exposed to aggressive chemical substances caustic acids solvents corrosive substances etc and avoid direct influence of weather conditions and direct sunlight 12 When fastening the system make sure not to damage other parts of the vehicle or the enclosure 1...

Page 8: ...100 min 1 Maximum pressure 60 bar 870 psi Power rating Angular connector All Current Resistive load AC 12 DC12 AC 250 V DC 24 V 4 A Inductive load AC 14 DC14 AC 250 V DC 24 V 2 A IP rating IP65 with cable connector and seal Electrical outlet DIN EN 175301 803 A Operation temperature from 20 C up to 80 C 4 F to 176 F Tested to EN60947 Low voltage switchgear and control gear IEC 68 2 78 Permissible ...

Page 9: ...er pressure in the tube and vice versa IMPORTANT At very low temperatures the pressure of agent vapours is close to zero Indicator on the pressure gauge can vary from 0 bar 0 psi when temperatures are very low to 17 bar 247 psi when temperatures are very high This is not a sign of defect in the system CASES WHEN THE BLAZECUT SYSTEM MUST BE REPLACED The system is leaking was used or emptied from ot...

Page 10: ... waste NEED SOMETHING MORE If there is a requirement for electronic monitoring external alarm or other size of system these are available Please contact technical blazecutgroup com GLOBAL HEAD OFFICE BlazeCut Pty Ltd 45 Evans St Balmain NSW 2041 Australia Tel 61 2 8006 1300 MANUFACTURER BlazeCut s r o Priemyselná 2521 90027 Bernolákovo Slovakia www blazecut com technical blazecutgroup com BlazeCut...

Reviews: