3.

 

Place the BlazeCut T Series in the proximity of the protected enclosure where the risk of fire is greatest (in the area of 
engines,  systems  containing  flammable  liquids  or  gases,  protected  objects,  electrical  installations,  connections,  circuit 
breakers, inductors, batteries etc.). 

 
4.

 

Bend the tube to shape for the installation. A minimum bend radius of 160 mm (6.30 in) must be maintained. 

 
5.

 

The BlazeCut T Series cannot directly contact parts or be in proximity to parts that heat to temperatures exceeding 90 °C 
(194 °F) during operation (e.g. engine, turbocharger, exhaust manifold, hot parts of inductors etc.). 

 
6.

 

If there are doubts on the operating temperature exceeding 90 °C (194 °F), measure the max ambient heat in the area 
where the tube is to be installed. The tube may not be in direct proximity, but the radiant heat rising to the top of the engine 
bay or enclosure may exceed the maximum 90 °C (194 °F) limit, causing a false actuation. 

 
7.

 

For maximum efficiency, do not place the BlazeCut T Series behind barriers that could restrict or prevent direct penetration 
of extinguishing agent into the protected enclosure. 

 
8.

 

Proceed carefully with the installation, so no damage is caused to the tube by sharp objects. Do not break or crimp the 
tube.  Make  sure  that the tube will not  damage  after closing the  doors or covers of the  enclosure (e.g.  after  closing the 
engine hood, installation of covers or enclosure etc.). No part of the system should be hit by moving parts (engine fans 
etc.). 

 
9.

 

The BlazeCut T Series must be firmly mounted in the protected enclosure so that it does not move. Use included cable ties 
or  PVC  dipped/rubber  insulated  metal  clamps.  The  maximum  distance  between  the  mounts  shall  not  be  more  than 
250 mm (9.84 in). 

 
10.

 

Fasten the system to fixed interior parts of the protected enclosure. Do not fasten to parts, which move during operation of 
the  vehicle  or  enclosure.  Make  sure  that  the  cable  ties  or  clamps  are  not  damaged  during  operation  of  the  vehicle  or 
enclosure. If  the BlazeCut T Series moves out  of  place  after installation,  the extinguishing  effect  of the system may be 
decreased and part or the entire protected enclosure may be damaged. 

 
11.

 

Install  the  system  so  that  it  is  not  exposed  to  aggressive  chemical  substances  (caustic,  acids,  solvents,  corrosive 
substances etc.) and avoid direct influence of weather conditions and direct sunlight. 

 
12.

 

When fastening the system, make sure not to damage other parts of the vehicle or the enclosure. 

 
13.

 

After installation, place the general warning label (ALA008) on a highly visible area

 

of the protected enclosure. The label 

should be placed on an even smooth surface. Clean the surface thoroughly before sticking. Do not place the label in areas 
reaching high temperatures (engine block etc.). 

 

T SERIES MODELS WITH INTEGRATED PRESSURE SWITCH 

The Pressure Switch models TxxxES and TxxxES-E, are mechanical switches with one pre-set pressure value (switch point). 
When the pressure in the system drops below the  switch point  the pressure  switch sends  a signal  to  an Alarm Panel or an 
external device to perform the designed operation. 
The Pressure Switch models TxxxES and TxxxES-E will send a signal when the pressure in the system decreases regardless 
of the cause 

– in case of fire or accidental activation or a decrease of pressure in the system which is below the pre-set value.  

The pressure switch can be used as a universal means of sending signal after a T Series system activation. External devices 
can  be informed via the signal  (alarm  panel, sounder,  beacon etc.)  or automatic processes can be performed (switching off 
electrical current, equipment shut-down etc.). 
Due to physical and chemical properties of the extinguishing agent, at very low ambient temperatures, the vapour pressure of 
the extinguishing agent could be zero and the pressure switch could send a false alarm signalling zero pressure. Due to this 
reason when the pressure switch is used on the system it is pressurized with a nitrogen (N

2

) so the pressure in the system shall 

not fall to zero. 
For more information about the pressure switch and its operation/functions please refer to the T Series Manual or contact your 
BlazeCut local agent. 
 

 

Models 

TxxxES 

Models 

TxxxES-E 

Indoor use 

 

 

Fixed applications 

 

 

Harsh environments 

 

×

 

Outdoor use 

 

×

 

Mobile/Vibrating applications 

 

× 

Switch monitoring 

 

× 

 

Summary of Contents for T Series

Page 1: ...FULLY This user manual contains important information about the BlazeCut T Series fire suppression system its use operation installation and maintenance If further technical information is required please request a copy of the T Series technical manual from a BlazeCut representative ...

Page 2: ...tely Following skin contact Flush irrigate the affected area with large amount of water Do not use hot water Remove contaminated clothing affected by extinguishing agent If you experience frostbite seek medical attention Following eye contact Carefully flush irrigate with water for several minutes If possible remove contact lenses if they are inserted Continue flushing Seek medical attention Follo...

Page 3: ...into one unit The BlazeCut T Series is not compatible with other fire suppression systems do not try to connect the system to any other equipment The system may be installed only by adult persons physically and mentally capable Incorrect interference with the system may cause malfunction of the system and provides threat to safety and health of people The system is under constant pressure any mech...

Page 4: ...18 ft3 0 11 lb 0 07 oz 11 02 in T050E 0 18 m3 0 14 m3 0 10 kg 2 g 53 cm 6 36 ft3 4 94 ft3 0 22 lb 0 07 oz 20 87 in T100E 0 46 m3 0 35 m3 0 25 kg 5 g 113 cm 16 24 ft3 12 36 ft3 0 55 lb 0 17 oz 44 48 in T200E 0 91 m3 0 69 m3 0 50 kg 5 g 215 cm 32 14 ft3 24 37 ft3 1 10 lb 0 17 oz 84 64 in T300E 1 37 m3 1 04 m3 0 75 kg 10 g 319 cm 48 38 ft3 36 73 ft3 1 65 lb 0 35 oz 125 59 in T400E 1 82 m3 1 39 m3 1 0...

Page 5: ...oisonous unnecessary excessive exposure of persons to its influence should be avoided Under no circumstances should persons be exposed to the extinguishing agent for more than 5 minutes also in case when the extinguishing concentration does not exceed the LOAEL level contact your local BlazeCut supplier for more information During the system activation the extinguishing agent is discharged from th...

Page 6: ... with the letter S in model designation have an integrated pressure switch that allows connection of signalling devices or to perform a shutdown operation at agent discharge An IP65 Pressure Switch is factory fitted for outdoor and mobile applications T Series models with the letters S E in model designation have an integrated economy pressure switch that allows connection of signalling devices or...

Page 7: ...ishing effect of the system may be decreased and part or the entire protected enclosure may be damaged 11 Install the system so that it is not exposed to aggressive chemical substances caustic acids solvents corrosive substances etc and avoid direct influence of weather conditions and direct sunlight 12 When fastening the system make sure not to damage other parts of the vehicle or the enclosure 1...

Page 8: ...100 min 1 Maximum pressure 60 bar 870 psi Power rating Angular connector All Current Resistive load AC 12 DC12 AC 250 V DC 24 V 4 A Inductive load AC 14 DC14 AC 250 V DC 24 V 2 A IP rating IP65 with cable connector and seal Electrical outlet DIN EN 175301 803 A Operation temperature from 20 C up to 80 C 4 F to 176 F Tested to EN60947 Low voltage switchgear and control gear IEC 68 2 78 Permissible ...

Page 9: ...er pressure in the tube and vice versa IMPORTANT At very low temperatures the pressure of agent vapours is close to zero Indicator on the pressure gauge can vary from 0 bar 0 psi when temperatures are very low to 17 bar 247 psi when temperatures are very high This is not a sign of defect in the system CASES WHEN THE BLAZECUT SYSTEM MUST BE REPLACED The system is leaking was used or emptied from ot...

Page 10: ... waste NEED SOMETHING MORE If there is a requirement for electronic monitoring external alarm or other size of system these are available Please contact technical blazecutgroup com GLOBAL HEAD OFFICE BlazeCut Pty Ltd 45 Evans St Balmain NSW 2041 Australia Tel 61 2 8006 1300 MANUFACTURER BlazeCut s r o Priemyselná 2521 90027 Bernolákovo Slovakia www blazecut com technical blazecutgroup com BlazeCut...

Reviews: