While mounting the unit consider the need to ensure sufficient service
access to the unit.
The unit must be mounted to a smooth-faced wall. Mounting of the unit to
an uneven surface results in the unit casing distortion and will prevent the unit
proper functioning.
The installation place must have connection to the sewage drain system.
While planning the ductwork layout avoid too long air duct sections,
numerous bends and reducers because it may reduce air flow.
The mounted air ducts must not be deformed.
Provide airtight connection of the air ducts to the unit spigots and fittings.
The unit mounting position must provide condensate drainage and access
to the terminal box for electric connection and access to the detachable service
panel for maintenance and filter replacement.
While mounting install a ventilation grille, an outer hood, a disk valve or
any other protecting device at outlet from the air duct with a mesh width not
exceeding 12.5 mm.
The unit mounting is as follows, fig. 3:
fix the wall mounted fixing bracket with the anchor bolts at the required
height using the fixing components from the delivery set.
hang up the unit on the wall-mounted fixing bracket.
To ensure correct supply air heating function install a duct temperature
sensor at least 1 m away from the supply air duct to spigot connection.
The duct supply air temperature sensor is mounted as follows:
Drill a Ø9 mm hole in the air duct.
Install a sensor in the hole.
Fix the sensor in place.
Ensure airtight connection of the sensor and the air duct joint.
MOUNTING
!
Safety precautions:
The unit must be mounted to a rigid and stable structure.
Before starting mounting check that the mounting structure has sufficient loading capacity for the unit weight.
The unit mounting is allowed only after power cut-off and full stop of the rotating parts.
Restrictions:
Do not operate the unit beyond the determined temperatures, in aggressive and in explosive medias. Do not connect the
clothes dryer or other similar equipment to the ventilation system.
Do not use the unit for air/dust mixture handling.
WARNING
Installation of the wall-mounted control panel:
Unlock the latches with a screw driver through the openings in the
bottom of the wall-mounted control panel, fig. 4.
Remove the back cover.
Disconnect the cable from the terminal block.
Route the cable in the wall to the control panel installation site.
Fix the control panel back cover to the wall, fig. 5.
Connect the cable to the terminal block.
Install the front part of the control panel on the latches.
Fig. 3. Unit mounting
Fig. 4. Removal of the control panel back cover
Fig. 5. Control panel back cover mounting to the wall