KOMFORT EC SKE270-1.5
CONDENSATE DRAIN
The drain pan is equipped with a drain pipe for condensate removal
outside the unit.
Connect the drain pipe, the U-trap (not included into the delivery set) and
a sewage system with metal, plastic or rubber drain hoses, fig. 6.
While laying the hoses provide the slope downward min. 3%.
Fill the system with water prior to connecting it to power supply. The
U-trap must always be filled with water.
Before starting the unit fill the drain system with water and keep the
U-trap always filled with water. Provide free drainage for the condensed
water, otherwise it is accumulated inside the unit which may result in the
equipment damage and condensate outflow to the room.
The condensate drain system is suitable for indoor frost-free
application with the ambient temperature above 0°C!
If the expected ambient temperature is below 0°C provide heating
for the drain system.
WARNING
In case of several unit mounting connect each unit to an individual U-trap. Direct condensate discharge with no connection to
the drain system is not allowed.
!
Fig. 6. Condensate drainage mounting
min 100 mm
min 50 mm
DRAIN PIPE
CONNECTING PIPE
U-TRAP
SEWAGE SYSTEM
min 3°
min 3°
CONNECTING PIPE