24
Extension cables
Cable length
Cross section
≤ 16 A
≤ 32 A
≤ 63 A
≤ 125 A
Calculated at a pre-fuse GG:
16amp*
32amp*
63amp*
125amp*
> 20m
1.5 mm²
2.5 mm²
10 mm²
25 mm²
20m > 50m
2.5 mm²
4 mm²
10 mm²
25 mm²
50m > 75m
4 mm²
6 mm²
16 mm²
35 mm²
*The cross-sections need to be re-calculated when using any other type or size pre-fuse than mentioned.