Black Box ME500A Manual Download Page 25

24

ASYNC/SYNC INDUSTRIAL LINE DRIVER

5.4.2 R

EMOTE

D

IGITAL

L

OOPBACK

(RDL)

The Remote Digital Loopback (RDL) test checks the performance of both the
local and remote Line Drivers and the communication link between them. In this
test mode, any characters sent to the remote Async/Sync Industrial Line Driver will
be returned back to the originating device. For example, characters typed on the
keyboard of the local terminal will appear on the local terminal screen after having
been passed to the remote Line Driver and looped back.

To perform an RDL test:

1. Activate RDL. You can do this in one of two ways: By moving the front-panel

toggle switch to Remote or by raising pin 21 on the RS-232 interface (make
sure DIP-switch S3-6 is ON and DIP-switch S2-6 is OFF).

2. Perform a BER-test (bit error rate) 511/511E test on the system. If the BER-test

equipment indicates a fault, and the Local Analog Loopback test was
successful for both Line Drivers, you may have a problem with the twisted-pair
line between the Line Drivers. Test the twisted-pair line for proper
connections and continuity.

5.4.3 U

SING THE

V.52 BER T

EST

I

NDEPENDENTLY

The V.52 BER test can be used independently of the V.54 loopback tests. This
requires two operators: one to initiate and monitor the test at the local Line Driver,
and one at the remote Line Driver.

To use the V.52 BER test by itself, both operators should simultaneously follow
these steps:

1. Locate the 511/511E toggle switch on the front panel and move it UP. This

activates the V.52 BER test mode and transmits a 511 test pattern to the other
Line Driver. If any errors are present, the receiving Line Driver’s red ERROR
LED will blink sporadically. 

NOTE

For this test to work, the 511 switch on both Line Drivers must be on.

2. If the test indicates no errors are present, move the V.52 toggle switch DOWN,

activating the 511/E test with periodic errors present. If the test is working
properly, the receiving Line Driver’s yellow ERROR LED will blink regularly. A
successful 511/E test will confirm that the link is in place, and that the Line
Driver’s built-in 511 generator and detector are working properly.

Summary of Contents for ME500A

Page 1: ...s a day 7 days a week Call 724 746 5500 or fax 724 746 0746 Mailing address Black Box Corporation 1000 Park Drive Lawrence PA 15055 1018 Web site www blackbox com E mail info blackbox com SEPTEMBER 19...

Page 2: ...KS TRADEMARKS USED IN THIS MANUAL AT T is a registered trademark of American Telephone and Telegraph Company Any other trademarks used in this manual are acknowledged to be the property of the tradema...

Page 3: ...n the equipment is operated in a commercial environment Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to...

Page 4: ...ato el ctrico debe ser montado a la pared o al techo s lo como sea recomendado por el fabricante 8 Servicio El usuario no debe intentar dar servicio al equipo el ctrico m s all a lo descrito en las in...

Page 5: ...de existir una antena externa deber ser localizada lejos de las lineas de energia 16 El cable de corriente deber ser desconectado del cuando el equipo no sea usado por un largo periodo de tiempo 17 C...

Page 6: ...2 1 Four Wire Cable Connection via RJ 45 18 4 3 Four Wire Multipoint Installation 19 4 3 1 Multipoint Twisted Pair Connection 20 4 4 RS 232 Connection 20 5 Operation 21 5 1 LED Status Monitors 21 5 1...

Page 7: ...RTS RTS CTS delay set to no delay 7 ms or 53 ms Applications Point to point or multipoint Indicators Mono color LEDs for TX RX RTS and CD Single LEDs for Power Test and Error RTS Anti Stream Timer 12...

Page 8: ...transformer isolation to guard against data loss due to ground potential differences and Silicon Avalanche Diode surge protection to guard against data line transients The Async Sync Industrial Line...

Page 9: ...r configuration The configuration switches allow you to select data rates clocking methods V 52 and V 54 tests word lengths extended signaling rates async or sync mode 2 or 4 wire operation anti strea...

Page 10: ...method The default settings are shown in the table below Table 3 1 S1 switches Position Function Factory Default S1 1 Data Rate On S1 2 Data Rate Off 9600 bps S1 3 Data Rate Off S1 4 Data Rate On S1 5...

Page 11: ...Off 2 4 Off Off On On Off 3 6 On On Off On Off 4 8 Off On Off On Off 7 2 On Off Off On Off 9 6 Off Off Off On Off 14 4 Off On Off On On 16 On On On Off Off 19 2 Off On On Off Off 28 8 Off Off Off On...

Page 12: ...allows for operation in switched carrier multipoint and or hardware handshaking applications S1 8 Setting Off Constantly On On Controlled by RTS 3 3 Configuration Switch Set S2 The DIP switches on S2...

Page 13: ...ariance from a given frequency level the Line Driver will tolerate S2 3 Setting Off 2 5 to 1 On 2 5 to 2 3 Switches S2 4 and S2 5 RTS CTS Delay The combined settings for switches S2 4 and S2 5 determi...

Page 14: ...control timing mode topology local loopback enable remote loopback enable and input impedance levels for the Async Sync Industrial Line Driver Factory default positions are shown in the table below Ta...

Page 15: ...n On 130 ohms On Off 200 ohms Off On 320 ohms Off Off High impedance minimum 2k ohms Table 3 5 Speed Selection Cable Gauge Data Rates kbps 1 2 1 8 2 4 3 6 4 8 7 2 9 6 14 4 19 AWG 0 9 mm 320 320 200 20...

Page 16: ...Setting On RS 232 initiation enabled Off RS 232 initiation disabled Switch S3 6 RS 232 Initiation of Remote Loopback Test The setting for switch S3 6 determines whether or not the Async Sync Industria...

Page 17: ...nnection Figure 4 1 shows the location of the RJ 45 jack on the Line Driver s rear panel Connect the wire to each Line Driver as described in the instructions that follow the illustration Figure 4 1 T...

Page 18: ...use the table below as a guide RJ 45 Signal 1 NC 2 GND 3 RCV 4 XMT 5 XMT 6 RCV 7 GND 8 NC Connection to ground is optional Proper wiring of pairs between the two Line Drivers is as follows Signal Pin...

Page 19: ...ing a daisychain or star topology 4 2 1 FOUR WIRE CABLE CONNECTION VIA RJ 45 The RJ 45 jack on an Async Sync Industrial Line Driver is prewired for a standard telco wiring environment To be sure you h...

Page 20: ...master Async Sync Industrial Line Driver transmits continually Initiation of two way communication is RTS controlled by each slave Async Sync Industrial Line Driver To facilitate multipoint communica...

Page 21: ...to wire the one pair and two pair cables properly for a star topology Note that the ground connection is not needed Host First Slave Second Slave XMT RCV RCV XMT RCV RCV RCV XMT XMT RCV XMT XMT Host...

Page 22: ...INDICATORS The Power LED lights green to signal that power is present The TX and RX indicators blink green with data activity Off indicates a low RS 232 logic level solid green indicates a high RS 23...

Page 23: ...timer begins to count when the DTE raises RTS If the time period that RTS remains high exceeds the preset time out period the anti stream circuit will force RTS low The Error LED will light red indica...

Page 24: ...on the keyboard of a terminal will appear on the terminal screen To perform a LAL test 1 Activate LAL You can do this in one of two ways by moving the front panel toggle switch to Local or by raising...

Page 25: ...h the twisted pair line between the Line Drivers Test the twisted pair line for proper connections and continuity 5 4 3 USING THE V 52 BER TEST INDEPENDENTLY The V 52 BER test can be used independentl...

Page 26: ...25 CHAPTER 5 Operation 5 5 Power Down To turn off the Async Sync Industrial Line Driver simply unplug the AC power cord from the wall There is no power switch...

Page 27: ...to reduce the potential difficulties in the field make sure that the cable being used has similar or better characteristics lower capacitance or lower resistance Table A 1 Distance in miles km Data Ra...

Page 28: ...e however distances may vary Resistance will also affect distance but not functionality Wire should be 26 AWG 0 4 mm or larger smaller AWG This Line Driver is designed to withstand normal environmenta...

Page 29: ...1000 Park Drive Lawrence PA 15055 1018 724 746 5500 Fax 724 746 0746 Copyright 1999 Black Box Corporation All rights reserved...

Reviews: