Changeover to simulations mode
Press «Sim1»
button
Press «Sim2»
button
Press «Sim2»
button
Press «Sim2»
button
Remarks
Changeover to simulation mode:
Press the Sim1 + Sim2 buttons
simultaneously for 2 seconds.
Mode
Sim1
2 seconds
+
Data
Sim2
2 Sekunden
1
Simulation mode:
Activation of the loop
1
Data
Sim2
1
Mode
Sim1
2
Data
Sim2
2
L0 -
No loop activation (time functions are active)
L1 -
Loop activation (time functions are active)
- Loop 1
- Loop 2
Activation of the output relay
Mode
Sim1
1
Data
Sim2
1
Mode
Sim1
2
Data
Sim2
2
0
0 -
Activation of output
0
1 -
Activation of output
- Loop 1
- Loop 2
Inductance of loop 1
Mode
Sim1
1
Measurement of the inductance, value in
µH
Inductance of loop 2
Mode
Sim1
2
Measurement of the inductance, value in
µH
Exiting simulation mode
Mode
Sim1
2 seconds
1
2
Return to function mode
If an error occurs, operating mode «A» and error display «E» light up alternately and an error code such as E 012 is displayed. The LED changes to
flashing red, the 4 most recent errors are stored and can be interrogated.
Display
E001
E002
E011
E012
E101
E102
E201/E202 E301
E302
E311
E312
Error
Interruption
Loop 1
Interruption
Loop 2
Short circuit
Loop 1
Short circuit
Loop 2
Under -
voltage
Over-
voltage
Saving
error
Loop 1
too large
Loop 2
too large
Loop 1
too small
Loop 2
too small
Briefly pressing the «Data» button shows the last of 4 errors on the display. Another short press switches to the error before that, and so on. When
the button is pressed for the 5th time, the device switches back to automatic mode. If you press the «Data» button for 4 seconds during the query,
all error messages are deleted. The figure shows memory slot 1 in which error 001, Interruption loop 1, has been stored (example).
Loop detector DI1-Pro V2 / DI2-Pro V2
Supply voltage /
Power consumption
24 VAC -20 % to +10%, max. 2 VA
24 VDC -10 % to +20%, max. 1.5 W
100-240 VAC ± 10%, 50/60 Hz, max. 2.9 VA
Loop inductance
max. 20 to 1000 µH,
ideally 80 to 300 µH
Loop connection wiring
At 20-40 µH: max. 100 m at 1.5 mm
2
At >40 µH: max. 200 m with 1.5 mm
2
min. twisted 20x/m
Loop resistance
< 8 Ohm with connection wire
Output relay (loop)
max. 240 VAC; 2 A / 30 VDC; 1 A; AC-1
Dimensions
22.5 x 94 x 88 mm (B x H x T)
Housing mounting
Direct DIN rail mounting
Connection type
Plug-in terminals
Protection class
IP 20
Approvals, safety
See declaration of conformity at www.bircher-reglomat.com
Operating temperature
-20°C to +60°C
Storage temperature
-40°C to +70°C
Air humidity
<95% non-condensing
Manufacturer: Bircher Reglomat AG, Wiesengasse 20, CH-8222 Beringen declares that the
Product, type: DI1-Pro V2, DI2-Pro V2
Model: 24V ACDC, LVAC, 1-loop devices, 2-loop devices
Intended purpose: Programmable loop detector for controlling gates and barriers as well as for regulating and counting cars in parking areas
if used in accordance with the intended purpose, complies with the basic requirements acc. to:
R&TTE Directive, Appendix III 1999/5/EC
5
Simulation mode
6
Troubleshooting
7
Reset
8
Most important technical data
9
Declaration of conformity
Mode
Sim1
2 Sekunden
Reset 1 (recalibration)
The loop(s) is/are recalibrated.
Mode
Sim1
8 Sekunden
Data
Sim2
Reset 2 (factory setting)
All values (except the error memory) are reset to the factory
settings (see Table 4.11a). The loop(s) is/are recalibrated.
88