UF V (E3) 09/2018
Page 92/116
24.4 Maintenance work by the customer
24.4.1 Checking and cleaning / replacing the condenser air filter
The condenser air filter prevents accumulation of dust on the condenser. If the filter is blocked by dust this
may cause decrease or failure of refrigeration.
Check the air filter visually for soiling every month. Especially with the alarm message “Condenser temp.“
(chap. 14.1) the filter may be soiled. You can rinse the filter and use it again.
Regularly check the filter visually for soiling.
The filter is located behind the air filter flap (E) in the lower housing cover. You can easily take it out for
cleaning or replacement.
•
Unscrew the quick locking screws (E2) of the air filter flap (E) and remove the air filter flap
•
Remove the condenser air filter (E1).
•
Wash the condenser air filter with water and let it dry. If necessary, replace the filter (Art. no. 6014-
0037).
•
Insert the condenser air filter and mount the air filter flap. Mount the quick locking screws.
(E2)
(E2)
(E1)
(E)
Figure 27: Removing the condenser air filter
(E)
Air filter flap
(E1) Condenser air filter
(E2) Quick locking screws
Fix the condenser air filter and the air filter flap correctly following cleaning or replacement