UF V (E3) 09/2018
Page 77/116
20.2 Activating the service setpoint
Required access level: “User”.
Path:
Normal display
Setpoints
Functions on/off
Service setpoint on/off
Path with optional CO
2
emergency cooling:
Normal display
Setpoints
Functions on/off
Service setpoint on/off
Press the
OK button
to enable the setting.
Setting function 3 “Service setpoint on/off”.
The current setting flashes. Use the
arrow buttons
to select between 1
(Service setpoint active) und 0 (Service setpoint not active).
Confirm the setting with the
OK button
.
Service setpoint on
With the
Back button
you can go back to the “
Functions on/off
” submenu and, repeatedly pressing it, to
Normal display
.
Normal display with the information message “Service setpoint active”.
Service setpoint acti
The service setpoint will remain active until manually deactivating function 3 “Service setpoint on/off”.