Redline Operating Manual RE / RF / RI 12/2010
page 34/46
Password request
Main menu
(e.g. Standby)
1 sec.
1 sec.
PASSCCODE
Entering the adjustment values (reference values)
Now you can call up the adjustment menu via the functional button to select adjustment values, and then
the lower adjustment value using the arrow keys. If you want to enter a reference value for the lower
adjustment value, press the functional button. The display automatically reverts to the main menu.
Adjustment menu
(selection menu)
Adjustment menu
(lower adjustment
value)
Main menu
(e.g. Standby)
5 x
USER
CALIBRATION
Call up again the adjustment menu. “C.ADJ” is displayed. Enter the value, which has been measured with
the reference measuring device at the lower adjustment value, using the arrow keys. The controller takes
over the value and shows again the adjustment menu (selection menu).
Example for lower adjustment value: controller shows 30 °C, reference measuring device shows 32 °C.
Adjustment menu
(reference value entry)
Adjustment menu
(reference value entry)
Adjustment menu
(selection menu)
5 x
or
CALIBRATION
ADJUST
CALIBRATION
ADJUST
USER
CALIBRATION