KBF-S (E6) 08/2018
page 36/88
Example:
Desired temperature value: 40 °C, desired safety controller value: 45 °C.
Possible settings for this example:
Temperature set point
Safety controller mode
Safety controller value
40 °C
Limit
Limit value 45 °C
Offset
Offset value 5 °C
10.2.1 Setting the safety controller mode
Required access level: “User”.
Path:
Normal display
Setpoints
Safety controller
Mode
Press the
OK button
to enable the setting.
Setting the safety controller mode
The current setting flashes. Use the
arrow buttons
to select between
LIMI (Limit) and OFFS (Offset).
Confirm the setting with the
OK button
.
Mode
With the
arrow-down button
you proceed to setting the safety controller value (chap. 10.2.2)
With the
Back button
you can go back to the “
Safety controller
” submenu and, repeatedly pressing it, to
Normal display
.
10.2.2 Setting the safety controller value
Required access level: “User”.
The desired safety controller mode must be selected first (chap. 10.2.1). Depending on the mode setting,
one of the following setting menus will appear.
Path:
Normal display
Setpoints
Safety controller
Limit
or
Offset
Press the
OK button
to enable the setting.
Setting the safety controller value with “Limit” safety controller mode.
The current value flashes. Enter the desired limit value with the
arrow
buttons
.
Confirm the entry with the
OK button
.
Limit
or
Setting the safety controller value with “Offset” safety controller mode.
The current value flashes. Enter the desired offset value with the
ar-
row buttons
.
Confirm the entry with the
OK button
.
Offset
Summary of Contents for KBF-S 240
Page 75: ...KBF S E6 08 2018 page 75 88 24 7 Dimensions Dimensions size 240...
Page 76: ...KBF S E6 08 2018 page 76 88 Dimensions size 720...
Page 78: ...KBF S E6 08 2018 page 78 88...
Page 79: ...KBF S E6 08 2018 page 79 88...
Page 81: ...KBF S E6 08 2018 page 81 88...
Page 82: ...KBF S E6 08 2018 page 82 88 26 Product registration...
Page 89: ......