BIJUR DELIMON INTERNATIONAL
OPERATORS MANUAL
CLP
36917 r#1
Controller Programming
Operation Mode Cont.
Cycle Control Mode (d 3) Continued
Example 2
– Configure CLP for Cycle Switch Mode 5 cycles on, and 60 minutes off (expect cycles to be complete in max. 2 minutes)
o
Open protective flap on motor cover to access the programming keys.
o
Hold down the S and R keys until the d mode is flashing.
o
Jog the
key until 3 is flashing, and hit the S key to enter C mode
o
Jog the
key on the flashing digit until 5 is displayed.
o
Hit the
key to move cursor to next digit.
o
Jog the
key on the flashing digit until 0 is displayed.
o
Hit the
key to move cursor to final digit.
o
Jog the
key on the flashing digit until 0 is displayed.
o
Hit the S key (Value of 5 cycles now saved), to enter P mode.
o
Jog the
key until 0 is flashing, and hit the
key
o
Jog the
key until 2 is flashing, and hit the
key
o
Jog the
key until 1 is flashing, and hit the S key
(Value of “120” seconds now saved for monitor time)
o
Jog the
key until 0 is flashing, and hit the
key
o
Jog the
key until 6 is flashing, and hit the
key
o
Successively set the next 2 digits to 0.
o
Hit the S key (value of 60 now saved) to enter FC mode
o
Jog the
key until 2 is flashing, and hit the S key (Units of minutes, now saved)
o
Finally hit the R key to enter run mode.
o
Close protective flap on motor cover.
ATTENTION:
IF LLPP or HHPP DISPLAYED WHEN REPLACING CONTROLLER:
+
+
LLPP+will+be+on+the+if+12V+is+to+a+24V+controller.
+
+
HHPP+will+be+on+the+if+24V+is+to+a+12V+cont
+
To+s
+
Hold+the+
+&+
+b(and+keep+them),+you+will+see+the+i.e.++L-24.+
+
Then+while+still+
+&+
+bhit+the
S button
+to+to+the+other+value+i.e.+L-12,+and+then+the++
+&+
+.++++
+
The+new+is+now+saved.