WWW.BIGASSSOLUTIONS.COM © 2016 DELTA T CORP. ALL RIGHTS RESERVED.
31
Junction Box
(in wall)
Mounting Plate
(fits standard junction box)
Auxiliary
Controller
Controller Cover
Button Cover
(optional)
a
b
3.85” (9.8 cm)
7.25” (18.4 cm)
Depth: 1” (2.5 cm)
A. Select a mounting location
Adhere to the following guidelines when selecting the auxiliary controller location:
• Install the auxiliary controller on a flat surface that is readily accessible, free from
vibration, and where there is adequate distance from foreign objects or moving
equipment.
• Do not mount the auxiliary controller adjacent to or above a heat source.
• Ambient temperature must be 14° F to 122° F (-10° C to 50° C) with a relative humidity
range of 0% to 95% non-condensing.
• Do not expose the auxiliary controller to a corrosive atmosphere or direct sunlight.
• When mounting the auxiliary controller, keep in mind that the fan should be visible
from the auxiliary controller location.
• A minimum distance of 6” (15.2 cm) should be maintained between controllers.
B. Mount the auxiliary controller
1. Route power wiring to the mounting location.
2. Attach the mounting plate to the junction box in the wall with the 6-32 x 1-1/4” screws (a) as shown below.
3. Pull the RJ-11 connector (not shown) through the junction box and mounting plate.
4. Rest the auxiliary controller in the cover, and then connect the data cable (not shown). Secure the cover to the
mounting plate with the four (4) provided 6-32 x 3/8” screws (b) as shown below.
5. (Optional) Snap the button cover onto the controller cover. Only the Up Arrow, Down Arrow, RUN, and STOP/
RESET buttons should be visible. The button cover can easily be removed to access other buttons.
13. Mount the Auxiliary Controller
WARNING: To reduce the risk of electric shock, wiring should be performed by a qualified electrician!
Incorrect assembly can cause electric shock or damage the motor and the auxiliary controller!
ATTENTION
The auxiliary controller is required for fan operation.