10b. Mount the Upper Temperature Sensor (to Wood Beam)
CAUTION: The wall controller and remote temperature sensor contain sensitive electronic PCBs. Use
extreme care when handling! ESD precautions recommended.
ATTENTION
Do not lose the rubber grommet during installation.
A. Select a mounting location
Do not mount the upper sensor in the following locations:
• Adjacent to or above radiant heaters
• Near HVAC ventilation intakes or exhausts
• On poorly insulated exterior walls
• In roof decking
• Near radiant heat sources
See “Wall Control Overview” to ensure proper mounting location.
B. Mount the upper temperature sensor
1. Route power wiring to the mounting location.
2. Loosen the (4) screws and remove the cover from the remote sensor.
3. Using the back of the sensor as a template, mark the (2) screw locations on the mounting surface.
4. Loosely install the mounting screws on the mounting surface in the hole locations.
5. Slide the remote over the screws, and then tighten the screws.
Before reattaching the front cover, complete the wiring
. See steps 12a–12b for details and wiring diagrams.
Note: The upper temperature sensor can be mounted in any orientation.
Front
Cover
Upper
Temperature
Sensor
Front Cover
Screws
Mounting Screws
(for wooden structures only)