- 62 -
INST
ALLA
TION
COMMISSIONING
Fig. 7.37
•
Press keys 11
and
13 (Fig. 7.35) at the
same time until the value of parameter 10
(30=180 seconds) is displayed on the LCD
display (Fig. 7.38).
Fig. 7.38
•
It is possible to modify parameter 10 by
00=
0s to
99=
600s using keys 12
or
13
(each increase or reduction by a unit on the
display corresponds to 6 seconds).
•
By pressing key 11 (Fig. 7.35) confirmation
of the inserted value is obtained.
•
Press keys 11
and
12 (Fig. 7.35) at the
same time to exit without changing the val
-
ue (return to the parameters list Fig. 7.37).
•
Press keys 11
-
12
-
13 (Fig. 7.35) at the
same time for 10 seconds to exit the "pro
-
gramming mode".
Programming using the REMOTE control
Act on the programming of the REMOTE con
-
trol to select a minimum time between two ig
-
nitions when the boiler functions in normal on/
off heating mode.
•
Press button for more than 3 seconds to
enter in
mode (Fig. 7.39).
Fig. 7.39
0
2
1
8
1
21
1 5
6
3
9
•
Press buttons
and
at the same
time to enter transparent programming (Fig.
7.40).
Fig. 7.40
•
Press buttons
or
to display the
"
PM10
" program for selecting the ignition
frequency (Fig. 7.41).
Fig. 7.41
In Fig. 7.41 a SET programmed at
90
is dis-
played corresponding to a re-ignition time of
about 3 minutes.