![BGH GMV-1015WM/G-X Technical Sales Manual Download Page 77](http://html1.mh-extra.com/html/bgh/gmv-1015wm-g-x/gmv-1015wm-g-x_technical-sales-manual_2746748077.webp)
Co
m
binatio
n
Outdoor air
temp
Indoor air temperature
℃
DB
16
18
20
21
22
24
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
℃
DB
℃
WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
120%
-19.8
-20.0
37.2
9.69
37.1
10.28
37.1
10.74
37.0
11.02
37.1
11.36
37.0
12.02
-18.8
-19.0
37.5
9.81
37.5
10.40
37.4
10.67
37.4
11.12
37.4
11.46
37.3
12.10
-16.7
-17.0
38.2
9.98
38.1
10.55
38.1
10.89
38.0
11.22
38.0
11.53
38.0
12.13
-13.7
-15.0
38.9
10.14
38.8
10.66
38.7
11.02
38.8
11.32
38.7
11.58
38.7
12.15
-11.8
-13.0
39.5
10.27
39.4
10.72
39.4
11.05
39.4
11.33
39.3
11.62
39.3
12.11
-9.8
-11.0
40.2
10.36
40.1
10.81
40.0
11.07
40.1
11.37
40.0
11.59
40.0
12.11
-9.5
-10.0
40.5
10.37
40.4
10.81
40.3
11.08
40.4
11.34
40.3
11.47
40.3
12.04
-8.5
-9.1
40.8
10.42
40.8
10.84
40.7
11.06
40.7
11.32
40.7
11.58
40.6
12.04
-7.0
-7.6
41.3
10.45
41.2
10.78
41.1
11.03
41.2
11.26
41.1
11.50
41.0
11.89
-5.0
-5.6
44.0
10.89
43.9
11.28
43.8
11.51
43.8
11.71
43.8
11.93
43.7
12.32
-3.0
-3.7
44.6
10.86
44.5
11.18
44.4
11.35
44.4
11.56
44.3
11.79
44.3
12.13
0.0
-0.7
45.6
10.73
45.5
11.01
45.4
11.28
45.4
11.33
45.3
11.53
45.3
11.84
3.0
2.2
48.4
10.94
48.2
11.20
48.2
11.33
48.1
11.49
48.1
11.65
47.1
11.62
5.0
4.1
50.8
11.18
50.7
11.43
50.7
11.54
50.5
11.70
50.5
11.85
47.1
10.91
7.0
6.0
53.4
11.41
53.4
11.65
53.2
11.75
52.4
11.61
50.7
11.17
47.1
10.27
9.0
7.9
56.1
11.64
56.0
11.86
54.1
11.34
52.4
10.92
50.7
10.50
47.1
9.67
11.0
9.8
59.0
11.84
57.5
11.63
54.1
10.67
52.4
10.28
50.7
9.89
47.1
9.12
13.0
11.8
61.1
11.72
57.5
10.91
54.1
10.01
52.4
9.66
50.7
9.30
47.1
8.57
15.0
13.7
61.1
11.04
57.5
10.28
54.1
9.45
52.4
9.11
50.7
8.77
47.1
8.10
18.0
16.8
61.1
10.43
57.5
9.73
54.1
8.98
52.4
8.63
50.7
8.31
47.1
7.68
20.0
18.5
61.1
9.88
57.5
9.29
54.1
8.59
52.4
8.23
50.7
7.92
47.1
7.31
24.0
20.5
61.1
9.40
57.5
8.91
54.1
8.28
52.4
7.89
50.7
7.60
47.1
7.01
110%
-19.8
-20.0
37.1
10.56
37.1
11.12
37.0
11.50
37.0
11.78
37.0
12.09
36.9
12.71
-18.8
-19.0
37.5
10.67
37.4
11.16
37.4
11.52
37.3
11.80
37.3
12.16
37.3
12.70
-16.7
-17.0
38.1
10.79
38.1
11.31
38.0
11.59
37.9
11.90
38.0
12.21
37.9
12.76
-13.7
-15.0
38.8
10.89
38.7
11.39
38.7
11.68
38.6
11.93
38.7
12.21
38.6
12.74
-11.8
-13.0
39.4
11.00
39.4
11.40
39.3
11.67
39.2
11.89
39.3
12.21
39.2
12.66
-9.8
-11.0
40.1
11.02
40.0
11.44
40.0
11.63
39.9
11.90
40.0
12.14
39.9
12.56
-9.5
-10.0
40.4
11.00
40.3
11.40
40.3
11.64
40.2
11.85
40.3
12.08
40.2
12.53
-8.5
-9.1
40.8
11.03
40.7
11.43
40.7
11.60
40.6
11.80
40.6
12.08
40.6
12.46
-7.0
-7.6
41.2
11.01
41.1
11.32
41.1
11.52
41.1
11.75
41.0
11.80
41.0
12.35
-5.0
-5.6
43.9
11.45
43.8
11.81
43.7
11.96
43.7
12.18
43.7
11.81
42.7
12.50
-3.0
-3.7
44.4
11.35
44.4
11.63
44.3
11.80
44.3
11.99
44.5
11.33
41.1
11.65
0.0
-0.7
45.4
11.15
45.4
11.40
45.3
11.54
45.3
11.71
46.4
11.67
43.2
11.48
3.0
2.2
48.2
11.33
48.1
11.57
48.1
11.66
48.0
11.80
46.4
11.36
43.2
10.45
5.0
4.1
50.7
11.55
50.7
11.79
49.7
11.53
48.0
11.10
46.4
10.69
43.2
9.83
7.0
6.0
53.2
11.76
52.8
11.84
49.7
10.84
48.0
10.44
46.4
10.05
43.2
9.25
9.0
7.9
56.0
11.95
52.8
11.13
49.7
10.20
48.0
9.83
46.4
9.46
43.2
8.72
11.0
9.8
56.0
11.24
52.8
10.47
49.7
9.61
48.0
9.26
46.4
8.92
43.2
8.23
13.0
11.8
56.0
10.54
52.8
9.82
49.7
9.04
48.0
8.72
46.4
8.39
43.2
7.75
15.0
13.7
56.0
9.94
52.8
9.26
49.7
8.54
48.0
8.23
46.4
7.94
43.2
7.34
18.0
16.8
56.0
9.40
52.8
8.78
49.7
7.79
48.0
7.80
46.4
7.56
43.2
6.99
20.0
18.5
56.0
8.92
52.8
8.35
49.7
7.39
48.0
7.43
46.4
7.25
43.2
6.68
24.0
20.5
56.0
8.52
52.8
7.97
49.7
7.04
48.0
7.11
46.4
6.99
43.2
6.43
GMV6 DC Inverter VRF Units
Technical Sales Guide
75