4.3 Correction of capacity along with ambient temperature and
configuration ratio
Rectification of cooling capacity
:
GMV-224WM/G-X
TC—Total capacity of outdoor unit; PI—Power input of outdoor unit
Co
m
binatio
n
Outdoor
air temp
(℃
DB
)
Indoor air temp
14.0
℃
WB
17.0
℃
WB
18.0
℃
WB
19.0
℃
WB
20.0
℃
WB
22.0
℃
WB
24.0
℃
WB
20.0
℃
DB
24.0
℃
DB
26.0
℃
DB
27.0
℃
DB
28.0
℃
DB
30.0
℃
DB
32.0
℃
DB
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
135%
-5
19.82
2.22
23.60
2.70
28.01
2.74
28.44
2.74
28.95
2.76
30.67
2.80
30.43
2.83
0
19.82
2.22
23.60
2.71
28.01
2.74
28.44
2.74
28.95
2.77
30.67
2.80
30.43
2.83
4
19.82
2.23
23.60
2.72
28.01
2.75
28.44
2.75
28.95
2.78
30.67
2.81
30.43
2.84
7
19.82
2.27
23.60
2.77
28.01
2.80
28.44
2.81
28.95
2.83
30.41
2.86
30.43
2.89
10
19.82
2.31
23.60
2.83
28.01
3.36
28.44
3.42
28.76
3.37
29.50
3.23
30.21
3.08
12
19.82
2.35
23.60
2.88
28.01
3.43
28.03
3.40
28.44
3.35
29.09
3.20
29.81
3.15
14
19.82
2.40
23.60
2.94
27.93
3.47
27.71
3.39
28.03
3.33
28.77
3.30
29.48
3.34
16
19.82
2.44
23.60
3.00
27.60
3.46
27.31
3.42
27.63
3.44
28.36
3.48
29.08
3.51
18
19.82
2.49
23.60
3.06
27.19
3.59
26.91
3.59
27.31
3.63
28.03
3.66
28.76
3.69
20
19.82
2.54
23.60
3.25
26.78
3.76
26.58
3.77
26.91
3.80
27.63
3.84
28.36
3.88
21
19.82
2.61
23.60
3.37
26.61
3.85
26.42
3.85
26.75
3.89
27.47
3.93
28.20
3.96
23
19.82
2.80
23.60
3.61
26.28
4.03
26.02
4.03
26.34
4.07
27.07
4.11
27.79
4.15
25
19.82
2.99
23.60
3.87
25.87
4.20
25.70
4.20
26.02
4.25
26.75
4.29
27.47
4.33
27
19.82
3.19
23.60
4.14
25.54
3.70
25.30
4.39
25.62
4.42
26.34
4.47
27.07
4.52
29
19.82
3.41
23.60
4.42
25.13
4.55
24.89
4.56
25.30
4.61
26.02
4.65
26.75
4.70
31
19.82
3.64
23.52
4.68
24.72
4.74
24.57
4.74
24.89
4.78
25.62
4.84
26.34
4.89
33
19.82
3.88
23.12
4.86
24.39
4.90
24.17
4.92
24.57
4.97
25.30
5.02
25.94
5.08
35
19.82
4.13
22.72
5.03
23.98
5.09
23.85
5.10
24.17
5.15
24.89
5.21
25.62
5.26
37
19.82
4.40
22.40
5.22
23.65
5.28
23.87
5.28
23.89
5.34
24.49
5.40
25.22
5.46
39
19.82
4.68
21.99
5.39
23.23
5.45
23.87
5.46
24.07
5.52
24.17
5.58
24.89
5.65
41
19.82
5.21
22.72
6.34
23.98
6.42
23.85
5.92
23.91
5.97
24.05
6.04
24.41
6.11
43
19.82
5.43
23.47
6.61
24.08
6.77
23.82
6.29
23.76
6.20
24.10
6.19
23.93
6.26
44
19.19
5.66
22.31
6.90
23.09
7.13
23.42
6.18
23.74
6.43
23.97
6.35
24.08
6.42
46
18.20
7.33
21.37
8.22
22.49
7.37
22.63
6.58
23.12
6.71
23.34
6.67
23.56
6.74
47
17.71
8.16
20.90
8.89
22.19
7.49
22.23
6.78
22.80
6.85
23.02
6.82
23.30
6.89
50
15.10
7.91
18.28
8.76
19.77
7.90
20.18
7.35
20.92
7.31
21.73
7.29
22.18
7.21
52
9.62
4.76
12.94
5.93
16.01
6.67
17.63
7.00
17.71
6.77
18.14
6.68
19.16
6.86
53
8.01
3.96
10.65
4.87
13.97
5.82
15.24
6.05
15.50
5.92
16.10
5.93
16.69
5.97
55
7.49
3.71
9.71
4.44
12.69
5.28
13.46
5.34
14.05
5.37
14.73
5.42
15.41
5.52
16
Summary of Contents for GMV-1015WM/G-X
Page 104: ...102...
Page 105: ...GMV6 DC Inverter VRF Units Technical Sales Guide 103...
Page 106: ...104...
Page 107: ...GMV6 DC Inverter VRF Units Technical Sales Guide 105...
Page 108: ...106...
Page 130: ...128...