MIZAR UL - Ver. 04 - 

7

D811137_04

ENGLISH

Thank you for buying this product, our company is sure that you will be more
than satisfied with the product’s performance. The product is supplied with
a “

WARNINGS

” leaflet and an “

INSTRUCTION MANUAL

”.

These should both be read carefully as they provide important information
about safety, installation, operation and maintenance. This product complies
with the recognised technical standards and safety regulations. We declare
that this product is in conformity with the following  Directives: CAN/CSA-
C22.2 No. 247-92  UL Std. No. 325

1) GENERAL OUTLINE
MIZAR UL

 mod. control unit has been designed to control one single

operator.

2) GENERAL SAFETY
WARNING! An incorrect installation or improper use of the product
can cause damage to persons, animals or things.

The “

Warnings

” leaflet and “

Instruction booklet

” supplied with this

product should be read carefully as they provide important information
about safety, installation, use and maintenance.

Scrap packing materials (plastic, cardboard, polystyrene etc) according
to the provisions set out by current standards. Keep nylon or polystyrene
bags out of children’s reach.

Keep the instructions together with the technical brochure for future
reference.

This product was exclusively designed and manufactured for the use
specified in the present documentation. Any other use not specified in
this documentation could damage the product and be dangerous.

The Company declines all responsibility for any consequences resulting
from improper use of the product, or use which is different from that
expected and specified in the present documentation.

Do not install the product in explosive atmosphere.

The Company declines all responsibility for any consequences resulting
from failure to observe Good Technical Practice when constructing
closing structures (door, gates etc.), as well as from any deformation
which might occur during use.

Disconnect the electrical power supply before carrying out any work on
the installation. Also disconnect any buffer batteries, if fitted.

Fit an omnipolar or magnetothermal switch on the mains power supply,
having a contact opening distance equal to or greater than 3mm.

Check that a differential switch with a 0.03A threshold is fitted just
before the power supply mains.

Check that earthing is carried out correctly: connect all metal parts for
closure (doors, gates etc.) and all system components provided with an
earth terminal.

The Company declines all responsibility with respect to the automation
safety and correct operation when other manufacturers’ components
are used.

Only use original parts for any maintenance or repair operation.

Do not modify the automation components, unless explicitly authorised
by the company.

Instruct the product user about the control systems provided and the
manual opening operation in case of emergency.

Do not allow persons or children to remain in the automation operation
area.

Keep radio control or other control devices out of children’s reach, in
order to avoid unintentional automation activation.

The user must avoid any attempt to carry out work or repair on the
automation system, and always request the assistance of qualified
personnel.

Anything which is not expressly provided for in the present instructions,
is not allowed.

 INSTALL THE GATE OPERATOR ONLY WHEN:

The operator is appropriate for the construction of the gate and the
usage Class of the gate,

All exposed pinch points are eliminated or guarded,

The operator is intended for installation only on gates used for
vehicles. Pedestrians must supplied with a separate access opening,

The gate must be installed in a location so that enough clearance is
supplied between the gate and adjacent structures when opening
and closing to reduce the risk of entrapment. Swinging gates shall
not open into public access areas,

The gate must be properly installed and work freely in both directions
prior to the installation of the gate operator. Do not over-tighten the
operator clutch or presure relief valve to compensate for a damaged
gate.

FOR GATE OPENERS WITH HOLD-TO-RUN CONTROL:

The gate operator controls must be placed so that the user has full
view of the gate area when the gate is moving,

A sign with the message “WARNING” must be positioned near the
controls. The characters for the writing should be at least 6.4 mm
high. The following statement should also be indicated: “Moving
Gate Has the Potential of Inflicting Injury or Death - Do Not Start Gate
Unless Path is Clear”.

An automatic closing device (such as a timer, loop sensor, or similare
device) shall not be employed

No other activation device shall be connected.

Controls must be far enough from the gate so that the user is prevented from
coming in contact with the gate while operating the controls. controls
intended to be used to reset an operator after 2 sequential activations of the
entrapment protection device or devices must  be located in the line-of-sight
of the gate. Outdoor or easly accesible controls shall have a security feature
to prevent unauthorized use.
All warnings signs and placards must be installed where visible in the area
of the gate.

FOR GATE OPENERS PROVIDED WITH SENSOR FOR CONTACT-
FREE DETECTION:

See instructions on the placement of non contact sensor for each
type of application,

Care shall be exercised to reduce the risk of nuisance tripping, such
as when a vheicle, trips the sensor while the gate is still moving, and

One or more non-contact sensor shall be located where the risk of
entrapment or obstruction exist, such as the perimeter reachable by
a moving gate.

FOR GATE OPENERS PROVIDED WITH CONTACT DETECTION
(RUBBER EDGE OR SIMILAR):

On or more contact sensor shall be located at the pinch point of a
vehicular vertical pivot gate.

A hardwired contact sensor shall be located and its wiring arranged
so that the communication between the sensor and the gate operator
is not subjected to mechanical damage.

A wireless contact sensor  such as one that transimts radio frequency
(RF) signals the gate operator for entrapment protection functions
shall be located where the transimission of the signals are not
obscrtucted or impeded y building structure, natural landscaping or
similar obstruction. A wireless contact sensor shall function under
the intended end-use conditions.

 IMPORTANT SAFETY INSTRUCTIONS

WARNINGS: to reduce the risk of injury or death:

Read and follow all instructions

.

Never let children operate or play with gate control. Keep the remote
control away from children.

Always keep people and objects away from the gate. 

NO ONE

SHOULD

CROSS THE PATH OF THE MOVING GATE

.

Test the gate operator montly. The gate MUST reverse on contact
with a rigid object activates the non-contact sensor. After adjusting
the force or the limit of travel, reset the gate operator. Failure to adjust
and retest the gate operator properly can increase the risk of injury
or death.

Use the emergency realease only when the gate is not moving.

KEEP GATES PROPERLY MAINTAINED

. Read the owners manual.

Have a qualified service person make repairs to gate hardware.

The entrance is for veichles only. Pedestrians must use separate
entrance.

Save these instructions.

3) TECHNICAL SPECIFICATIONS

Power supply: ........................................................ 120V~ 

±

10% 60Hz  (*)

Loadless absorption: ....................................................................  400 mA
Accessory output power: ............................................ 24Vac 200 mA max
Max. motor power absorbed: ........................................................... 500W
Limits switch: ....................................................................... electric switch
Working time: ....................................................... adjustable from 1 to 90s
Control panel dimensions: ...........................................................  See fig.1
Case protection: ................................................................................  IP54
Working temperature: ............................................................... -20 +55 

°

C

(*) Special voltages on request.

INSTALLATION MANUAL

ENGLISH

Summary of Contents for MIZAR UL

Page 1: ... Lago di Vico 44 36015 Schio VI Tel naz 0445 696511 Tel int 39 0445 696533 Fax 39 0445 696522 Internet www bft it E mail sales bft it ISTRUZIONI D USO E DI INSTALLAZIONE INSTALLATION AND USER S MANUAL INSTRUCTIONS D UTILISATION ET D INSTALLATION INSTRUCCIONES DE USO Y DE INSTALACION MIZAR UL 8 027908 113115 ...

Page 2: ...2 MIZAR UL Ver 04 D811137_04 ...

Page 3: ...vamente e commercialmente il prodotto senza impegnarsi ad aggiornare la presente pubblicazione USER S MANUAL ENGLISH Thank you for buying this product our company is sure that you will be more than satisfied with the product s performance The product is supplied with a WARNINGS leaflet and an INSTRUCTION MANUAL These should both be read carefully as they provide important information about safety ...

Page 4: ...nvenientes para mejorar técnica constructiva y comercialmente el producto sin la obligación de poner al día esta publicación MANUEL D UTILISATION Nous vous remercions pour avoir choisi ce produit nous sommes sûrs qu il vous rendra le service nécessaire à vos besoins Lisez attentivement le livret AVERTISSEMENTS et le MANUEL D INSTRUCTIONS qui accompagnent ce produit puisqu ils fournissent d importa...

Page 5: ...amento I cancelli a battente non potranno essere aperti in aree di pubblico accesso Il cancello deve essere installato correttamente e deve funzionare liberamente in entrambe le direzioni prima dell installazione dell apricancello Nonserrareeccessivamentelafrizionedell attuatore o la valvola di sfiato della pressione per rimediare ad un cancello danneggiato IN CASO DI APRICANCELLI CON COMANDO UOMO...

Page 6: ...serisce il TCA dopo stop va in apertura Con Dip Fix IBL in ON qualsiasi comando di start in fase di apertura non ha alcun effetto 62 Logica a 2 passi disponibile a richiesta Un comando di start ha i seguenti effetti cancello chiuso apre in apertura ferma ed inserisce il TCA Dip Fix TCA ON cancello aperto chiude in chiusura apre dopo stop apre 7 SELEZIONE DIP FIX Fig 3 TCA Tempo di chiusura automat...

Page 7: ... is supplied between the gate and adjacent structures when opening and closing to reduce the risk of entrapment Swinging gates shall not open into public access areas The gate must be properly installed and work freely in both directions prior to the installation of the gate operator Do not over tighten the operator clutch or presure relief valve to compensate for a damaged gate FOR GATE OPENERS W...

Page 8: ...llowing actions take place after a start command closed gate opens opening stops and operated the TCA Dip Fix TCA ON open gate closes closing opens after the stop opens 7 DIP FIX SELECTION Fig 3 TCA Automatic closing time TCA ON Automatic closing on OFF Automatic closing off IBL Blocks impulses ON START commands are not accepted during the opening phase OFF START commands are accepted during the o...

Page 9: ...ons il faut prévoir des accès séparés Le portail doit être installé dans une position telle à assurer une distance suffisante entre le portail et les structures adjacentes pendant l ouverture et la fermeture afin de réduire le risque de coincement Les portails battants ne pourront être ouverts dans des aires d accès public Le portail doit être installé correctement et il doit fonctionner librement...

Page 10: ...vants portail fermé ouvre en ouverture arrête et insère le TCA Dip Fix TCA ON portail ouvert ouvre en fermeture bloque arrête et n insère pas le TCA après le stop va en ouverture Avec Dip Fix IBL sur ON aucune commande de start dans la phase d ouverture ne produit un effet 6 2 Logique à 2 pas disponible sur demande Une commande de start a les effets suivants portail fermé ouvre en ouverture arrête...

Page 11: ...ever accesos separados La cancela debe instalarse en una posición que garantice una distancia suficiente entre la misma y las estructuras adyacentes durante las fases de apertura y de cierre para reducir el riesgo de aprisionamiento Las cancelas batientes no podrán abrirse en áreas de público acceso Lacanceladebeinstalarsecorrectamenteydebefuncionarlibremente en las dos direcciones antes de la ins...

Page 12: ... abre en fase de apertura para y conecta el TCA Dip Fix TCA ON cancela abierta cierra en fase de cierre bloquea para y no conecta el TCA después de un stop abre Con Dip Fix IBL en ON ninguna orden de start en fase de apertura tiene efecto alguno 6 2 Lógica de 2 pasos disponible a petición Una orden de start tiene los siguientes efectos cancela cerrada abre en fase de apertura para y conecta el TCA...

Page 13: ...DF1 IBL DF2 PCL DF3 10 11 12 13 14 15 16 17 18 19 20 21 LD5 LD4 LD3 LD2 LD1 LD6 LD7 PROT SWO SWC STOP ST OP CL MIZAR UL MB 4 92 125mm 7 20 183mm 7 67 195mm 8 85 225mm ø 5 m m ø 0 1 9 3 54 90mm 1 2 3 4 5 6 7 8 9 L N GND M1 BLINK 40W max 10 11 12 13 14 15 16 17 18 19 20 21 START COM NO NC NC NC NC STOP ANT SWC II CH R 24 V PHOT SW0 ANT SHIELD 24 V EBP 120 V ...

Page 14: ...ANTENNA 21 FL50 FL100 BARRA SENSIBLE PERFIL SENSÍVELPERFIL SENSÍVEL SICHERHEITSLEISTE BARRE PALPEUSE SENSITIVE EDGE COSTA SENSIBILE COMM NC SWO SWC FOTOCELULAS FOTOCÉLULAS PHOTOZELLE PHOTOCELLULES PHOTOCELLULES PHOTOCELLULES FOTOCELLULE FOTOCELLULE 5 4 1 2 3 2 1 TX2 RX2 TX1 RX1 24Vac Fig 5 Fig 6 ME MIZAR 12V 1 2 4 3 16 15 14 13 12 11 10 5 4 3 2 1 6 SS 12V 3W 1 2 4 3 MIZAR 18 17 16 15 14 13 12 120 ...

Page 15: ...MIZAR UL Ver 04 15 D811137_04 ...

Page 16: ...BFT S p a ITALIA Via Lago di Vico 44 36015 Schio VI Tel naz 0445 696511 Tel int 39 0445 696533 Fax 39 0445 696522 Internet www bft it E mail sales bft it ...

Reviews: