Operation of the Compact Flame Controller
6-1
6
Operation of the Compact Flame
Controller
Danger of injury and material damage if improperly used!
Improper use of the compact flame controller can lead to
injury or even death and to material damage!
Operation of the compact flame controller only by author-
ised and qualified special personnel!
Observe the operating instructions!
The response of the compact flame controller depends on
the burner configuration as well as on the air flow and the
spectral characteristic (wave length).
6.1
Test of the Compact Flame Controller
In order to ensure correct operation, the compact flame
controller must be tested several times for all applications
by starting and stopping the burner several times (the
flame relay must reliably shut-down in all cases when
there is no flame). Carry out these tests whilst several
neighbouring burners are started and stopped and differ-
ent boiler outputs are used. This is an indispensable pre-
requisite for a safe and correct operation of the device!