Transport, Installation and Connection
4-12
4.10.2
Terminal diagram
A – Harting device plug (pin contacts)
B – Harting cable connection box (socket contacts)
Connection of standard compact flame controller with special cable KW5
Internal
External
Con-
tact
Conduc-
tor colour
Function
Burner
control
mA
display
Power supply
1
wh
Flame relay lead
x
2
br
Flame relay Flame ON
x
3
pk
Flame relay Flame OFF
x
4
gn
Power 24V DC
+24V DC/200mA
5
ye
Power supply GND
-
GND
6
gr
Analog (0/4 to 20 mA)
+
Connection of compact flame controller with internal heating (optional)
(only with special cable KW6)
Internal
External
Con-
tact
Conduc-
tor colour
Function
Burner
control
mA
display
Power supply
1 - 6 as for standard controller
7
bl
Power supply to heater (-)
GND
8
rd
Power supply to heater (+)
+24V DC / 500mA
B
A
Automa-
tionAutoma-
tech n olo gy for yo ur future
BFI
Type
Ser.-No.:
24Vdc
Germany
CFC 2000
Summary of Contents for CFC 200
Page 2: ......
Page 11: ...General aspects 1 7 1 8 Declaration of conformity...
Page 20: ...Safety 2 8...
Page 26: ...Technical data 3 6...
Page 42: ...Transport Installation and Connection 4 16...
Page 46: ...Operation of the Compact Flame Controller 6 2...
Page 48: ...Care and Maintenance 7 2...
Page 50: ...Failures 8 2...
Page 52: ...Order data 9 2...
Page 54: ...Accessories 10 2...
Page 55: ...Accessories 10 3...