Transport, Installation and Connection
4-14
Contact-
insert
Crimp contact
inner PUR
jacket
outer shielding
outer PUR
jacket
Plastic insert
thread
union nut
single core
15
20
55
4.10.4
Laying the special cable KW5/KW6
It must not remain unequipped contact chambers. All con-
tact chambers have to be equipped with crimp contacts.
The outer shield is connected to the compact flame con-
troller side in a large area by a clamping connection be-
tween the plastic liner and the threaded portion of the
gland to the housing ground.
The inner shield is cut off on both sides.