Technical data
3-2
3.2
Electrical system, Optical and Mechanical Data
spectral sensitivity
CFC 200 UV1 (formerly 8.0) 190 bis 550 nm
CFC 200 UV (formerly 8.30) 280 bis 420 nm
CFC 200 IR (formerly 8.40) 300 bis 1050 nm
CFC 200 IR3 (formerly 8.70) 1050 bis 2700 nm
Sight view angle
2,7 °
Self monitoring
fully electronic
Operating voltage
24 V DC
Current consumption
approx. 200 mA
Design
according to class III SELV
Ambient temperature
-20 degrees to +70 degrees C
Current output
0/4…20 mA, Ra < 250
Ω
Flame relay
1 changeover contact, floating
VDE 0110, class A
max. 48 V switching voltage
max. 1 A switching current
(fused with 0.5 A)
max. 30 W switching power
Thresholds
„Flame ON“ 5 (8) mA
„Flame OFF“ < 5 (8) mA
Adjustment
with sensitivity potentiometer
Safety switch-off time
set by factory to 1 s
Sight view connection
1“ inner thread ISO 228
Purge air connection
½“ inner thread ISO 228
Purge air volume
10 m³/h