1-Way Traffic: Setting Up The Re-Entry Zone

 

 

 

The Ultraview sensor has a Re-Entry Zone function (see remote functions on Page 8) that  

 

 

 

 

allows the User to define a secondary sensitivity level for the purpose of re-entry that is 

 

 

 

independent of the normal microwave sensitivity. When using this function, the 0 value is off,  

 

 

 

 

while the values of 1 through 9 are the sensitivity levels - 9 being maximum sensitiv-

ity. When  

 

 

at a value of 1 through 9, the secondary activation pattern is defined, and the output 

from    

 

 

 

this zone is linked to the presence output from the sensor. Additionally, to aid 

in the setup,    

 

 

 

the sensor’s LED will show red when the Re-Entry Zone is in detec-

tion.

 

 

 

By default, the Re-Entry Zone sensitivity is set to 3. This will need to be fine-tuned    

 

 

 

 

per each application. To test the zone, perform the following:

 

 

 

1.

Place the rotary switch on the header to a 1-way traffic mode.

 

 

 

2.

Activate the door normally and proceed to the side not intended for use. Move to    

 

 

 

 

about 5’ away from the door.

 

 

 

3.

As soon as the door starts to close, walk slowly towards the Ultraview sensor.

 

 

 

4.

As you walk towards the sensor, the LED will turn green to indicate motion 

 

 

 

detection. However,the door will not re-cycle open at this time (it will continue to  

 

 

 

 

 

close), because the motion output is going to the Outer Impulse at the control box,    

 

 

 

 

which has been ignored due to the 1-way traffic selection.

 

 

 

5.

Continue walking toward the door. As soon as the LED turns red, the door should 

 

 

 

re-cycle open.The re-activation must occur at 24” or greater from the face of the sliding door. 

 

 

 

6.

If activation is at less than 24”, increase the Re-Entry Zone sensitivity and test  

 

 

 

 

 

again. Be sure to test the zone from all approach angles to insure the following:

 

 

 

Detection pattern must extend out from the face of the door to 24” or greater, as 

 

 

 

measured from the center of the clear door opening.

 

 

 

Detection pattern must extend for the full width of the clear door opening 

 

 

 

Detection pattern must be within 5” of the face of the sliding door as measured at  

 

 

 

 

 

the center of the opening.

 

 

 

7.

Remember, when the rotary switch is in the 1-way traffic mode, activation from the  

 

 

 

 

 

sensor at “the side not intended for use” will re-activate the door only if a detection is  

 

 

 

 

realized by the Re-Entry Zone, or by the infrared presence zone.

 

 

 

8.

Don’t forget to adjust normal microwave sensitivity for when the rotary switch is in   

 

 

 

 

a 2-way traffic mode. When the switch is placed back to the 2-way traffic mode, 

 

 

 

sensor indications will remain the same, however, activation from the normal   

 

 

 

 

 

microwave detection 
pattern will allow door 
activation.

 

(1 through 9 value ) Re-Entry Zone

(0 through 9 value ) Normal microwave zone

Summary of Contents for AAE977

Page 1: ...0 09 07 30 09 V4 Copyright 2009 Besam US Inc May not be reprinted without permission 1 Complies with ANSI BHMA A156 10 Standard for Power Operated Pedestrian Doors UL325 Listed Besam UltraView Install...

Page 2: ...r detection performance SPECIAL NOTE The Ultraivew works differently than the BEA Wizard When making changes to the Ultraview reference the Ultraview users guide If you inadvertently make changes base...

Page 3: ...roduct conformity R TTE 1999 5 EC EMC 89 336 EEC FCC Interface Factory Installed Technology Microwave and microprocessor Transmitter frequency 24 125 GHz Transmitter radiated power 20 dBm EIRP Transmi...

Page 4: ...connector on the Ultraview Interface Board Ultraview US23 0640 09 07 30 09 V4 Copyright 2009 Besam US Inc May not be reprinted without permission 4 MOUNTING SCREWS INFRARED LENS SHROUD SENSOR COVER U...

Page 5: ...the push button is released Then repeat step 2 5 Mechanically adjust the presence field of each sensor for the installation a Launch a setup of the system by momentarily pressing and releasing the rig...

Page 6: ...LENS FACTORY DEFAULT 6 6 W X13 75 D CHANGE PRESENCE LENS IF NEEDED REMOVE BEZEL OPTIONAL NARROW ANGLE ANTENNA ADJUST ANGLE BY TILTING MICROWAVE CELL 7 0 height 13 W X 6 6 D 6 6 W X 8 2 D Wide Narrow...

Page 7: ...t off main power to the Unislide wait 5 seconds 6 Re apply power 7 Unlock P1 press unlock then 1 8 Press magic wand on the remote control 9 Press 0 this will launch a set up Keep traffic away from the...

Page 8: ...rol 0 min 9 max default 7 Sensitivity Microwave Detection Mode 1 bidirectional mode 2 unidirectional mode 3 unidirectional mode with MTF Setup launch an assisted setup restore factory settings When re...

Page 9: ...he door will not re cycle open at this time it will continue to close because the motion output is going to the Outer Impulse at the control box which has been ignored due to the 1 way traffic selecti...

Page 10: ...eter being altered 1 flash means value 1 The right button enables selection of the parameter number being altered 1 for each press The left button enables alteration of the value 1 for each press EXAM...

Page 11: ...resence If LED s are illuminat ing make sensor adjustments as necessary to eliminate unwanted detection Check angle and sensitivity for presence and motion see pg6 2 Check for moving objects in the pa...

Page 12: ...pressing the reset button next to the 5 position switch 3 Select correct sensor with P1 1 Reset system to neutral 2 Power Off On by pressing the reset button next to the 5 position switch 3 Select co...

Page 13: ...ows the User to toggle between STD and AUX The STD position is the default position The AUX position is selected for applications that require initial activation by the Knowing Act device only Thus wh...

Page 14: ...cover position to the 1 way traffic mode The AUX input will not be acknowledged when placed in the STD position KNOWING ACT TO PUSH PLATES DRY CONTACT ONLY DIP SWITCH P1 P2 TO BREAKOUT SWITCHES 1 Wir...

Page 15: ...activation regardless of door position 3 Setting the rotary switch to the OFF position will disable all inputs once the door is fully closed c Part Time 1 Way Security Day Night Mode Set STD AUX swit...

Page 16: ...bottom guide assembly for proper adjustment and excessive wear 13 Check door closing speed and closing force 14 Check closing latch location 15 Check that door hold open time is 1 5 seconds or longer...

Reviews: