3.
Route the two connectors of the harness through the hole in the side of
the sensor and connect to the two headers on the circuit board.
4.
Attach the sensor to the header using the two Phillips head screws being
careful that the sensor wires do not obstruct the mounting of the sensor base.
Then, replace the shroud on the sensor.
5.
Repeat the installation procedure to the other side of the header.
6.
Attach the cover to the sensor only after all mechanical adjustments are made.
Electrical Installation
The Ultraview Interface Board located at the front of the Unislide control has an option to
allow the input of a ‘Knowing Act’ device, such as push plates. The input device must have a
dry contact switch connected to this point. A small switch next to the input allows the User
to toggle between STD and AUX. The STD position is the default position. The AUX position
is selected for applications that require initial activation by the Knowing Act device only. Thus
when the switch is set to AUX, the initial activation must be provided by the push plate
(or otherwise), then once the door is at a position other than fully closed, the Ultraview
sensors will function with respect to the IR curtains, as well as according to the microwave
Standard Input vs. Auxiliary Input
1.
Insert the Ultraview Interface Board into the Unislide Door Control and tighten all
of the screw terminals so that the Interface is securely fastened to the Control.
2.
Insert the connectors from the sensor harnesses to the board as labeled (see page 4).
3.
Set dip switch to position A. Position B is not active and will be used in future product
development.
Ultraview US23-0640-09