-14-
• Air stream too weak
• Air stream hits obstruction
• Negative pressure
• Shaft rotating inside fan
• One motor not operating
• Nozzle not angled out far enough
• Unit too powerful
• Air movement too cold
• Pushing air outside building
SEE AIR IS NOT HITTING FLOOR SYMPTOMS
• Switch turned to “ON” position
• Thermostat not set properly
• Coils burned out due to lack of air
• Automatic reset thermal cutout failed in open
position
• Manual reset thermal cutout tripped
(if supplied)
• Adjust nozzle to proper position, adjust motor
speed; see installation instructions
• Remove obstruction or reposition air curtain
(move out 3/8” for every 1” up from the door)
• Relieve negative pressure by providing makeup
air
• Tighten set screws
• Repair or replace motor
• Adjust nozzle angle to outside
• Adjust motor speed
• Add auxiliary heat to overcome wind chill factor
• Adjust discharge angle back into building, adjust
motor speed
• Replace switch or check wiring
• Change thermostat setting
• Correct airflow problem; replace coils
• Replace automatic thermal cutout
• Reset manual thermal cutout
AIR IS NOT HITTING
FLOOR
UNEVEN AIR
EXCESSIVE AIR
MOVEMENT AT
DOORWAY
ELECTRICALLY HEATED MODELS
NO HEAT
MINIMAL HEAT
EXCESSIVE HEAT
HOT WATER HEATED UNITS
EXCESSIVE HEAT
MINIMAL HEAT
NO AIR
• Power supply line open (no power)
• Fuse blown/circuit breaker tripped
• Motor overload tripped
• Failed switch
• Check power source, check service disconnect,
check method of control in ON position
• Replace fuse(s)/reset breaker
• Internally protected motor - should reset
automatically after cool-down, if not, replace motor.
• Replace switch
MOTOR RUNNING/FANS ARE NOT ROTATING
MINIMUM AIR
ELECTRICAL CONTROLS NOT FUNCTIONING WHEN DOOR IS OPEN
SYMPTOMS
REMEDY
CAUSE
• Broken or damaged flexible hub
• Shaft rotating inside fan
• Selector switch is in off position
• Door limit switch not operating
• Air directional discharge vanes mis-adjusted
• Inadequate intake clearance
• Blower motor operates below speed
• Fan rubbing against housing
• Fan wheels clogged with dirt
• Fan in backwards
• Replace fan sleeve/reengage coupling
• Tighten set screws/tighten fan on shaft
• Turn switch to “ON” position
• Repair or replace limit switch
• Adjust vanes to proper position, see instructions
• Move air curtain or remove obstruction
Provide adequate space for air curtain
• Improper voltage
• Free fan from housing
• Clean and vacuum fan wheels
• Check fans for blade curve toward discharge
• Thermostat in wrong location - thermostat
too close to discharge
• Improper voltage
• Thermostat not set properly
• Low entering air temperature
• Incorrect speed range
• Thermostat in wrong location
• Thermostat not set properly
• Insufficient air over coil
• Improper voltage
• Move thermostat away from air stream
• Supply proper voltage
• Change temperature setting
• Based on unit temperature rise, reduce speed
• Check Factory Menu speed range matches diagram
• Move the thermostat closer to air stream
• Change temperature setting
• Remove restriction on intake
• Supply proper voltage
• Reduce hot water flow
• Clean intake and coils
• Increase water flow
• Increase water flow
X. TROUBLESHOOTING
• Too high hot water pressure
• Inadequate air flow, fins plugged up, dirty coils
• Water temperature too low
• Intake air below design temperature