Standards and Certifications • Requirements for Immunity to Disturbances
Mobile Panel User's Manual V 1.5
4.6 Magnetic fields with energy technical frequencies
4.7 Voltage dips, fluctuations and short-term interruptions
DC power I/O
150 kHz - 80 MHz, 10 V, 80 %
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80 %
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80 %
amplitude modulation with 1 kHz,
Criteria A
Functional ground connections
0,15 - 80 MHz, 10 V, 80 %
amplitude modulation with 1 kHz,
Length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80 %
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
-
Signal connections >3 m
0,15 - 80 MHz, 10 V, 80 %
amplitude modulation with 1 kHz,
Length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80 %
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
150 kHz - 80 MHz, 3 V, 80 %
amplitude modulation with 1 kHz,
Criteria A
Test carried out according to
EN 61000-4-8
Limit values according to
EN 61000-6-2
Limit values according to
EN 61131-2
Limit values according to
EN 55024
Test direction x, test in the field of
an induction coil 1 m x 1 m
30 A/m, criteria A
30 A/m, criteria A
50 Hz, 1 A/m, criteria A
Test direction y, test in the field of
an induction coil 1 m x 1 m
30 A/m, criteria A
30 A/m, criteria A
50 Hz, 1 A/m, criteria A
Test direction z, test in the field of
an induction coil 1 m x 1 m
30 A/m, criteria A
30 A/m, criteria A
50 Hz, 1 A/m, criteria A
Table 43: Test requirement magnetic fields with energy technical frequencies
Test carried out according to
EN 61000-4-11
Limit values according to
EN 61000-6-2
Limit values according to
EN 61131-2
Limit values according to
EN 55024
AC power inputs
Voltage drop
70 % (30 % reduction), 0.5
periods, criteria B
-
Voltage drop
< 5 % (> 95 % reduction), 0.5 half-
oscillations, criteria B
AC power inputs
Voltage drop
40 % (60 % reduction), 5 periods,
criteria C
-
Voltage drop
70 % (30 % reduction), 25 half-
oscillations, criteria C
AC power inputs
Voltage drop
40 % (60 % reduction), 50
periods, criteria C
-
-
AC power inputs
Voltage Interruptions
< 5 % (> 95 % reduction), 250
periods, criteria C
-
Voltage Interruptions
< 5 % (> 95 % reduction), 250
half-oscillations, criteria C
AC power inputs
-
20 interruptions, 0.5 periods,
criteria A
-
DC power inputs
-
20 interruptions for 10 ms,
< UN - 15 %, criteria A
-
Table 44: Test requirement voltage dips, fluctuations and short-term interruptions
Test carried out according to
EN 61000-4-6
Limit values according to
EN 61000-6-2
Limit values according to
EN 61131-2
Limit values according to
EN 55024
Table 42: Test requirement conducted disturbances (cont.)
Summary of Contents for 4MP181.0843-03
Page 2: ...2 Mobile Panel User s Manual V 1 5...
Page 4: ...4 Mobile Panel User s Manual V 1 5...
Page 6: ...6 Mobile Panel User s Manual V 1 5...
Page 134: ...134 Accessories USB Memory Stick Mobile Panel User s Manual V 1 5...
Page 144: ...144 Maintenance Servicing Changing the Battery Mobile Panel User s Manual V 1 5...
Page 160: ...Model Number Index 160 Mobile Panel User s Manual V 1 5...