56
When the last digit is validated,
Save
is highlighted.
3.
Validate with
OK
on the left knob.
The confirmation screen appears.
4.
Select
YES
then validate with
OK
on the left knob.
The
Analog Input/Output
menu is then displayed.
5.6.5
Analog Input/Output Fail-Safe position
When a 4-20 mA input signal is used, it is possible to set up a fail-
safe position if the input signal is lost.
This function is active in the standard configuration and the actuator
remains in its position if the input signal is lost.
How to set the Position on Loss of Setpoint
1.
From
Analog Input/Output
menu, enter
Position on Loss of
Setpoint
.
The following screen appears.
2.
Select the desired value and validate with
OK
on the left knob.
3.
Navigate to
Save
and validate with
OK
on the left knob.
The confirmation screen appears.
4.
Select
YES
and validate with
OK
on the left knob.
The
Analog Input/Output
menu is then displayed.
This function cannot be used with 0-20 mA signals, as the
system cannot discern a lost signal from a 0-mA value.